Parker Balston GC-4000 Installation, Operation And Maintenance Manual Download Page 16

Bulletin TI-GCGS-E 

Installation, Operation and Maintenance Manual

Technical Information 

GC Gas Stations GC-4000, FID-4000

1-800-343-4048

16

Maintenance

When performing routine maintenance, carefully follow the instructions provided in this 

section to avoid injury or damage. Service should be performed by persons familiar with the 

service and safety requirements of electromechanical / electrochemical devices. 

The primary maintenance tasks required by the Parker Balston GC Gas Station are: changing 

the deionizer resin cartridge, changing the compressed air filter cartridge (annually), 

changing the zero air filter (annually), and replacing the catalyst module (3 years), replacing 

the water pump (3 years). Each of these components are readily accessible by removing the 

side panel of the generator.  A summary of the replacement part numbers and recommended 

Service frequency is shown at the end of the Maintenance section. See Figure 7 and 8 for the 

locations of the maintainable components. 

Additional coalescing compressed air prefilter cartridges and final filter cartridges for 

the Parker Balston GC Gas Stations may be ordered through your local representative. 

For convenience, the replacement filter cartridge, final filter, DI resin cartridge have been 

assembled into a maintenance kit. With proper care and maintenance, the GC Gas Station will 

provide years of trouble free operation. No adjustments or calibrations need to be made to the 

generator.  Only routine service is needed to maintain peak operational conditions. 

Before Servicing the Parker Balston GC Gas Station, isolate the unit from the compressed 

air source and electrical supplies.  Decrease hydrogen output pressure to zero.  Turn 

power switch, at the rear of the unit OFF and unplug.  

Warning:   Unit must cool down for 2 hours prior to any zero air catalyst or purifier service.

The compressed air filter is located on the outside rear panel of the generator.  Isolate the 

generator from the compressed air supply and let outlet pressure drop to zero.  The filter 

cartridge inside the housing should be changed on an annual basis to maintain efficient 

operation of the system.  Remove the filter cartridge housed in this filter assembly by 

unscrewing the filter bowl from the filter head.  Insert the new filter cartridge (P/N 050-05-BX) 
and re-assemble the filter housing in reverse order.

The zero air filter is located on the outside rear panel of the generator.  Isolate the generator 

from the compressed air supply and let outlet pressure drop to zero.  The GS050-05-95 filter is 

inside the housing and should be changed on an annual basis to maintain efficient operation of 

the system. Remove the filter cartridge housed in this filter assembly by unscrewing the filter 

bowl from the fil ter head. Insert the new filter cartridge (P/N GS050-05-95) and re-assemble 

the filter housing in reverse order. 

General

Compressed Air Filter 

Cartridge Replacement

Zero Air Filter Cartridge 

Replacement

Switch power OFF to unit and unplug generator from power.  Allow the compressed air 

to continue to flow through the unit to improve heat dissipation during cooling. Allow the 

generator to cool for at least 2 hours. 
Close the (customer installed) inlet air valve. 
Remove 6 screws from the right side cover.  See figure 8.
Remove Base Access cover from beneath the zero module- 2 screws. This allows the zero air 

module to be lowered away from the hydrogen purifier
Disconnect Catalyst Module connector located on rear, right side of the unit (see Figure 8). 

Make note of its orientation for replacement of the module.
Disconnect inlet and outlet air fittings, as shown in figure 8, using two 7/16” wrenches.  One 

wrench holds the fitting, while the other loosens the compression nut closest to the zero air 

module.

Zero Air Catalyst Module 

Replacement

Summary of Contents for GC-4000

Page 1: ...nt at 800 343 4048 8AM to 5PM Eastern Time or email at balstontechsupport parker com North America only For other locations please contact your local representative Do not use a Hydrogen gas storage v...

Page 2: ...ly into carbon dioxide and water The module is sized to deliver 4000 cc min of zero grade hydrocarbon free air to the instrumentation downstream The nal lter on the Parker Balston GC Gas Generator is...

Page 3: ...ation before the ADD WATER message is displayed However the generator will continue to operate for an additional 105 hours from the water in the main tank with the ADD WATER message displayed once the...

Page 4: ...erator must be between 60 F 100 F 16 C 40 C Do not place the generator where there is a chance of freezing Place the generator in an upright position on a level surface in close proximity to the elect...

Page 5: ...tor may be transported over short distances when lled Do not grasp the front panel Bezel when moving the generator lift only from the bottom Keep the generator in an upright position Remove all red ta...

Page 6: ...or Do not use plastic tubing downstream from the generator Out gassing from the plastic may contaminate the zero grade gas Use PTFE tape on all inlet and outlet NPT ttings Thread sealing compounds may...

Page 7: ...d by the operator then it will become disabled to prevent repeated un necessary actuation of the auto water feed solenoid valve To reactivate the auto water feed connect a source of deionized water to...

Page 8: ...eve hydrocarbon removal to 0 05 ppm see Figure 5 Power Up Start Up Sequence and Hydrogen flow at the specified flow rate 1 If the hydrogen line needs to be purged before the hydrogen can be used on th...

Page 9: ...Hydrogen and Zero Air 7 Time delay for Zero Air 90 minutes allows it to reach operating temperature Once time has expired the unit is ready to provide both Hydrogen and Zero Air 8 Open Hydrogen outle...

Page 10: ...r at least a week of continuous op eration Water can be added manually by removing the reservoir cap and slowly adding water to the Fill reservoir see the Water Reservoir section in Startup Reinstall...

Page 11: ...r status hydrogen flow and zero air status of the unit The 4 line display will show Hydrogen usage in of capacity So 100 display indicates 500cc min hydrogen is being produced by the cell Hydrogen pre...

Page 12: ...e GC Gas Station OFF and allow the Hydrogen gas to purge slowly until all the internal gas is removed 2 Then cap the Hydrogen outlet on the back of the generator or leave it connected to the downstrea...

Page 13: ...p Zero Air Module Air fittings Zero Air Catalyst Module Figure 8 Shown with side cover removed Left side Main Reservoir Drain Right side Fill Reservoir Drain Zero Air filter Fill Reservoir Deionizer R...

Page 14: ...r section to reactivate the auto water feed system Completely fill the Fill Reservoir with deionized water Once full and when water quality is verified by the generator s sensors the water is transfer...

Page 15: ...vel Generator will shut down if water level is below the EMPTY level Customer installed shutoff valve is closed open valve Check piping for leaks Consult factory Heater defect Low temperature Allow pu...

Page 16: ...r to any zero air catalyst or purifier service The compressed air filter is located on the outside rear panel of the generator Isolate the generator from the compressed air supply and let outlet press...

Page 17: ...m power Allow the compressed air to continue to flow through the unit to improve heat dissipation during cooling Purifier Zero Air module and cooling coil will be hot Allow unit to cool 2 hours before...

Page 18: ...er displayed The unit will automatically start to produce Hydrogen as soon as the LOW WATER LEVEL sensor is actuated If poor quality water is added to the generator a Change water message will be disp...

Page 19: ...trical hazard Do not use commercial leak detection uids on any Lexan plastic parts in the genera tor These uids may cause cracking and crazing which leads to part failure Use a solution of 4 5 ml of l...

Page 20: ...ided with the product then Parker guarantees at Parker s option to replace the product repair the product or refund the original price for the product This warranty applies only to defects in material...

Reviews: