Paragon Fires Focus RS Owner'S Manual Download Page 14

LT4548 (10:09/10) 

14

 

PARAGON FOCUS RS 

Installation Instructions 

 

SECTION EIGHT 

Siting the Appliance 

 
 (When  installing  in  a  timber  framed  dwelling  reference  must  be  made  to  the  specific  installation 
requirements stated in 

Section 10 Installing the Appliance in Timber Framed Dwelling

). 

 

THERE ARE TWO TYPES OF INSTALLATION

 (into conventional masonry walls): -   

 

The appliance body can be recessed back into the brickwork cavity so that the appliance is flush 
fitting with the wall or fireplace back panel, see Installation Instructions,  

OR 

 

With a dummy chimneybreast constructed forward into the room to take up the 180mm depth of 
the firebox. This depth can be reduced if a deep rebated surround is  also used the rebate depth 
can be deducted from the dummy breast depth 

Any  surround  used  must  meet  the  specification  stated  later  in  this  section.  Prior  to  installing  the 
appliance all combustible materials must be removed from the rear faces as described in Section 10.  

 

GENERAL REQUIREMENTS 

 

 

The  flue  and  air  duct  length 
must  be  between  100mm  to 
1metre.  The  fire  is  supplied 
with a standard pipe length of 
400mm  (to  be  cut  in  half  to 
make  a  flue  and  air  duct 
length  of  200mm)  The  flue 
and 

air 

duct 

must 

not 

accommodate 

any 

bends.  

Other  lengths  of  flue  and  air 
duct are available 

 

The flue outlet must terminate 
on a suitable outside wall.  

 

The  minimum  flue  terminal 
clearances,  which  must  be 
maintained, are as shown below.     

A  

Directly below an openable window or other opening. E.g. air brick   

300mm

 

 

Below gutters, soil pipes or drain pipes   

 

 

 

 

300mm

 

Below eaves  

 

 

 

 

 

 

 

 

300mm

 

Below balconies or car port roofs   

 

 

 

 

 

600mm

 

From vertical drain pipes and soil pipes   

 

 

 

 

75mm

 

From internal and external corners 

 

 

 

 

 

300mm

 

Above ground, roof or balcony level 

 

 

 

 

 

370mm

 

From a surface facing the terminal 

 

 

 

 

 

600mm

 

From a terminal facing the terminal 

 

 

 

 

 

1200mm

 

From an opening in a car port into a dwelling e.g. door, window, etc  

1200mm

 

Vertically from a terminal on the same wall 

 

 

 

 

1500mm 

Horizontally from a terminal on the same wall   

 

 

 

300mm   

Note: These dimensions are taken from the centre of the circular flue outlet. 
 
 
 
 

 

Summary of Contents for Focus RS

Page 1: ...INSET LIVE FUEL EFFECT GAS FIRE OWNER S MANUAL Please read these instructions carefully before you start using the appliance Keep this booklet handy for future reference This appliance is for use in...

Page 2: ...SECTION NINE Preparing the Appliance for Installation 15 SECTION TEN Install the appliance 16 Installing the Appliance into a Cavity Wall 16 Installing the Appliance into a Deep Rebated Surround or Du...

Page 3: ...s are not classified as hazardous waste and should be disposed of at a site licensed for the disposal of industrial waste The PARAGON FOCUS RS is an inset room sealed decorative fuel effect gas applia...

Page 4: ...first Run the fire on high over a few days The first time you light your new appliance a smell may occur due to its new condition This is quite normal and will soon disappear after a few hours use at...

Page 5: ...THREE Operation Do not use this appliance without the glass panel fitted or if this panel is cracked or broken WARNING If the burner or pilot is extinguished for any reason do not attempt to re light...

Page 6: ...Supermarkets Remove the glass panel as follows Remove ash pan cover and fret Remove decorative trim held in place with four magnets Slacken but do not remove the 4 nuts securing the bottom glass clam...

Page 7: ...BED PARTS SHOULD BE ADDED to the appliance If any Fuel Bed Parts are broken then they must be replaced before the appliance is used Note There are three possible fuel bed arrangements COAL PEBBLE or...

Page 8: ...as shown in the picture Position two A coals and three B coals as shown in the picture Finally position one A coal and two B coals as shown in the picture That completes the coal bed assembly Go to se...

Page 9: ...their underside 2B 4off 3B 1off 4B 2off 2G 2off 4G 3off The Rear Matrix is located so that it fits behind the burned ensure it is not placed over the burner The Front Matrix is located as shown in fro...

Page 10: ...anel and other associated parts are fitted before lighting the appliance The Driftwood set as shown consists of Rear Matrix Front Matrix Nine Individual Driftwood parts Marked on their underside D1 1o...

Page 11: ...d shapes shown with the marking placed below or to the rear of the shape That completes the pebbles bed assembly Go to section eleven to complete the appliance assembly Ensure the glass panel and othe...

Page 12: ...u may experience outing from cold In this case it may be necessary to remove the restrictor plate Please ensure that the flue pipe has been adequately sealed before undertaking removal of this plate M...

Page 13: ...ISH STANDARDS B S 5871 PART 2 B S 5440 PART 1 B S 6891 B S 1945 Note This appliance must be installed to current versions of the above standards and include any relevant amendments THE BUILDING REGULA...

Page 14: ...scribed in Section 10 GENERAL REQUIREMENTS The flue and air duct length must be between 100mm to 1metre The fire is supplied with a standard pipe length of 400mm to be cut in half to make a flue and a...

Page 15: ...00 mm provided fire is central to the surround and sides do not project more than 150 mm When vertical side forward projection is increased by 12 5 mm add 50 mm to inside width of surround Check with...

Page 16: ...zontal line at a height of 555mm above the hearth line joining the two outside lines together Mark the position for a lintel above the top horizontal line Mark two short horizontal lines so they cross...

Page 17: ...t it seals to both the flue pipe and the air duct use flue seal or fire cement to ensure air tight seal Drill through the four holes in the outer wall terminal plate and fix back to the wall using plu...

Page 18: ...ing account of the relative gas regulations appertaining to a gas pipe in a cavity Permanently fix the deep rebated surround in position and pack the void behind the fascia panel of the deep rebated s...

Page 19: ...diameter must be fitted to these clearance holes To ensure that any condensation formed on the duct pipes does not drip on to the inner wall a length of galvanised wire must wrapped around each flue p...

Page 20: ...e point at which the sleeved installation pipe enters the fire The Gas Safety Installation and Use Regulations Certificate of exemption number 1 of 1996 Where the pipe enters the fire the outer sleeve...

Page 21: ...able fire fret up to the appliance conforming to the requirements referred to in section one of this manual SECTION THIRTEEN Instruct and Advise the Customer Demonstrate the lighting and extinguishing...

Page 22: ...he left hand side 4 Disconnect the injector pipe from the left hand side of the gas control 5 Disconnect the pilot pipe from the underside of the pilot burner 9 Pull off the connection to the spark el...

Page 23: ...s and re commission Replacement of the Pilot Injector 1 Undo the pilot tube nut at the pilot bracket 2 Pull the pipe gently back taking care not to damage 3 Remove the pilot injector from inside the p...

Page 24: ...ust be installed by a CORGI registered person 2 The appliance must be used in accordance with the users instructions 3 The appliance must be serviced annually by a CORGI registered person 4 The servic...

Page 25: ..._______________ ___________________________________________ Date of Purchase Service Log The following information must be complete and supported by receipts as part of the conditions of the extended...

Page 26: ...LT4548 10 09 10 26...

Page 27: ...AILS Name ________________________________ Address ________________________________ Post Code TELEPHONE No PRODUCT DETAILS Model PARAGON FOCUS RS Serial No Date of Purchase This information can be fou...

Page 28: ...ssembly Air Test Completed Microswitch Check Warning Label Fire Guard Front Matrix 4607 Rear Matrix 4604 Pebble Set 4611 Installation Seal 2090 Restrictor Elbow 2189 Magnets 4 x 3048 Glass Panel Canop...

Reviews: