56
Programming Guide
Connecting Fire Circuits
Alarm Relay and PGM Connections
AC Power & Backup Battery Connections
Transformer Requirements
Transformer:
16VAC
20VA*
(Amseco XP-1620)
16.5VAC
40VA
(Universal
UB1640W)
*not verified by UL
DC Power
Supply rated at:
MG5000/MG5050 = 1.0A
SP5500/SP6000/SP7000 = 1.4A
Auxiliary Supply can
provide a maximum of:
typ: 600mA
max: 700mA
UL installations: typ. 200mA
Acceptable Battery
Charge Currents
(section [700] option
[2])
350mA/700mA
WARNING: It is recommended that the smoke
detectors be connected in a daisy chain
configuration. Each control panel (except the
SP5500) supports a maximum of five 2-wire
smoke detectors.
NOTE:
For 4-wire installation:
Program the Activation Event so that the smoke detectors can be reset by pressing the [
CLEAR
] + [
ENTER
]
keys for three seconds. See Event Group # 6 on page 30. For 2-wire installation (except SP5500): Press [
CLEAR
] + [
ENTER
] to
automatically reset smoke.
PGM Power Source
AUX + terminal
= must not exceed 700mA.
External power supply = PGM1 and PGM2 cannot exceed
100mA or cannot exceed the power
supply’s current limit.
Partial view of control panel
UL Warning: A 12Vdc / 7Ah battery is required to comply with
UL fire requirements.
WARNING: Improper connection of the transformer may result
in damage to the system.
WARNING: Disconnect battery before replacing the fuse.
Rechargeable Battery
UL/ULC - 12Vdc / 4Ah or 7Ah