Paradox Digiplex EVO PRT3 Programming Instructions Manual Download Page 3

2

Introduction

The PRT3 Printer Module can be used as an interface between C-Bus and your Digiplex system. When in home automation mode, the 
Printer Module can receive and send commands to and from the C-Bus PC interface and the Digiplex control panel, linking your building 
automation capabilities with your security system.

The Printer Module features 30 virtual PGMs for use with its building automation interface capabilities. These PGMs are not related to any 
physical output on the module, but operate in the same manner and are programmed in the same way as traditional PGMs. A virtual PGM 
can be used to trigger a response within C-Bus based on an event that has occurred within the Digiplex system. For example, when a user 
uses the Digiplex system to disarm an area, this event could activate a virtual PGM on the Printer Module and trigger a response within C-
Bus, such as turning on a specific light on the premises. See “Virtual PGM Programming” on page 4. 

Up to 30 C-Bus entries can be associated with the Printer Module’s virtual PGMs. C-Bus entries allow you to set the commands that will be 
sent on the C-Bus in relation to events that occur within the Digiplex system. When the state of a virtual PGM on the Printer Module 
changes, a message is sent by the C-Bus entry that is associated with that virtual PGM. See “C-Bus Entry Options” on page 8.

The Printer Module also features 16 onboard virtual inputs. These inputs are not related to any physical input on the module, but operate in 
the same manner and are programmed in the same way as a traditional zone input. A virtual input can be programmed to trigger a response 
from the Digiplex control panel based on an event that has occurred within C-Bus. Using virtual inputs to trigger events within the Digiplex 
control panel involves associating the Printer Module’s virtual input to a zone or a keyswitch on the control panel. See “Virtual Input Options” 
on page 14. 

 In order for C-Bus and the Digiplex control panel to communicate in such a way, the Printer Module’s serial port must be set to 
communicate using the Clipsal C-Bus Protocol.

For a complete list of the Printer Module’s event reporting features, see the Printer Module V1.0 (PRT3) Instructions.

The PRT3 Printer Module is compatible with C-Bus interface firmware V4.00.00 and higher. C-Bus lighting units must be configured
with firmware V1.1 and higher.

If the Printer Module fails to connect to the C-Bus PC interface, a trouble will be generated.

Installation

The Printer Module is connected to the control panel’s combus. Connect the four terminals labeled red, black, green, and yellow of the 
module to the corresponding terminals on the control panel as shown in Figure 2 on page 20. See the 

EVO or DGP-848

 

 Reference & 

Installation Manual

 for the maximum

 

allowable installation distance from the control panel.

The C-Bus PC Interface must be connected to the Printer Module’s serial port using a null modem cable only.

Overview

The following provides of an overview of how the Printer Module communicates with C-Bus.

Figure 1: C-Bus Overview

• Messages from C-Bus PC interface can be used to open/

close virtual inputs on the Printer Module.

• C-Bus entries are associated with Printer Module’s virtual 

PGMs.

• Printer Module sends messages to C-Bus PC interface based 

on virtual PGM events and C-Bus Entry programming.

Summary of Contents for Digiplex EVO PRT3

Page 1: ...Printer Module C Bus Programming Instructions We hope this product performs to your complete satisfaction Should you have any questions or comments please visit www paradox com and send us your comme...

Page 2: ...21 Technical Specifications Parallel Port Minimum 80 column printer Serial Port 1 start bit 8 data bit no parity and 1 stop bit 8N1 Input Voltage 9 16 Vdc Current Consumption 60mA maximum Serial Port...

Page 3: ...one input A virtual input can be programmed to trigger a response from the Digiplex control panel based on an event that has occurred within C Bus Using virtual inputs to trigger events within the Dig...

Page 4: ...ule to communicate with C Bus When this option is ON enabled you can connect the C Bus PC interface directly to the Printer Module s serial port 9 pins through the use of a null modem cable Set option...

Page 5: ...dix 1 Programming PGMs on page 21 Sections 070 to 072 C Bus Applications Section Application Hexadecimal Value 070 __ __ C Bus lighting Application 38 071 __ __ C Bus Air conditioning Application AC 0...

Page 6: ...20 13 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer 230 14 N no deactivation U deactivation event N virtual PGM timer N deactivation event or vir...

Page 7: ...s 310 22 U seconds N minutes 170 8 U seconds N minutes 320 23 U seconds N minutes 180 9 U seconds N minutes 330 24 U seconds N minutes 190 10 U seconds N minutes 340 25 U seconds N minutes 200 11 U se...

Page 8: ...__ __ __ 205 __ __ __ Virtual PGM12 212 __ __ __ 213 __ __ __ 214 __ __ __ 215 __ __ __ Virtual PGM13 222 __ __ __ 223 __ __ __ 224 __ __ __ 225 __ __ __ Virtual PGM14 232 __ __ __ 233 __ __ __ 234 __...

Page 9: ...al PGM15 246 __ __ __ 247 __ __ __ 248 __ __ __ 249 __ __ __ Virtual PGM16 256 __ __ __ 257 __ __ __ 258 __ __ __ 259 __ __ __ Virtual PGM17 266 __ __ __ 267 __ __ __ 268 __ __ __ 269 __ __ __ Virtual...

Page 10: ...16 550 557 22 610 617 28 670 677 5 440 447 11 500 507 17 560 567 23 620 627 29 680 687 6 450 457 12 510 517 18 570 577 24 630 637 30 690 697 Section 400 Option 1 Application Selection Section C Bus E...

Page 11: ...5 U none N on N off N ramp 550 16 U none N on N off N ramp 560 17 U none N on N off N ramp 570 18 U none N on N off N ramp 580 19 U none N on N off N ramp 590 20 U none N on N off N ramp 600 21 U none...

Page 12: ...U none N on N off N ramp 550 16 U none N on N off N ramp 560 17 U none N on N off N ramp 570 18 U none N on N off N ramp 580 19 U none N on N off N ramp 590 20 U none N on N off N ramp 600 21 U none N...

Page 13: ...5 502 11 652 26 512 12 662 27 522 13 672 28 532 14 682 29 542 15 692 30 Section 403 ON Ramp Period Not used with air conditioning Ramp Period Programmed Value Real Time Value Ramp Period Programmed Va...

Page 14: ...ntry an OFF Ramp Period 444 5 594 20 454 6 604 21 464 7 614 22 474 8 624 23 484 9 634 24 494 10 644 25 504 11 654 26 514 12 664 27 524 13 674 28 534 14 684 29 544 15 694 30 Section 405 OFF Group Addre...

Page 15: ...riable and type of command which will cause the virtual input to react open close The tables below offer an example of the virtual input programming sections which must be set for virtual input 1 526...

Page 16: ...6 3 720 726 7 760 766 11 800 806 15 840 846 4 730 736 8 770 776 12 810 816 16 850 856 Section 700 Option 1 Enabling Virtual Input Option Section Virtual Input 1 OFF 1 ON Section Virtual Input 1 OFF 1...

Page 17: ...nd N virtual input timer N close command or virtual input timer 780 9 U close command N virtual input timer N close command or virtual input timer 790 10 U close command N virtual input timer N close...

Page 18: ...oning 730 4 U seconds N minutes 810 12 U seconds N minutes 740 5 U seconds N minutes 820 13 U seconds N minutes 750 6 U seconds N minutes 830 14 U seconds N minutes 760 7 U seconds N minutes 840 15 U...

Page 19: ...l must be greater or equal to the threshold value To close a virtual input the Ramp s Final level must be lower than the threshold value Enter 000 255 to set the virtual input s threshold level Sectio...

Page 20: ...le 3 Entry Exit delay N Disable U Enable 4 Zone in alarm Zone in alarm restore zones 01 to 80 N Disable U Enable 5 Fire Alarm Fire Alarm Restore N Disable U Enable 6 Silent Alarm Report Silent Alarm R...

Page 21: ...serial port to a home automation module 6 9 pin Serial Port Connect C Bus to the Printer Module using a null modem cable 7 9 pin Serial Port Connect either the Printer Module s USB or 9 pin serial por...

Page 22: ...Timer Enter the section that corresponds to the desired PGM and enable or disable the option PGM Deactivation Event When the PGM Deactivation Option see above is disabled the PGM Deactivation Event de...

Page 23: ...000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 008 TX Delay Zone Alarm 000 Zone Numbers 001 t...

Page 24: ...witch Not Used Not Used 019 Alarm Cancelled with Master 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255...

Page 25: ...to 255 001 User Codes 256 to 511 001 to 255 001 to 255 002 User Codes 512 to 767 001 to 255 001 to 255 003 User Codes 768 to 999 001 to 231 001 to 231 255 Any User Code Not Used Not Used 032 Zone Shu...

Page 26: ...192 001 to 192 255 Any zone number Not Used Not Used 044 Zone Supervision Trouble Restored 000 Zone Numbers 001 to 192 001 to 192 255 Any zone number Not Used Not Used 045 Special Events 000 Power up...

Page 27: ...to 254 255 Any module Not Used Not Used 059 Module Manually Removed From Combus 000 Module Address 001 to 254 001 to 254 255 Any module Not Used Not Used 060 061 Future Use Future Use Future Use Futu...

Page 28: ...TE 4 This event cannot be used for a module s PGM programming If a Keyswitch Input is used the input must be defined as Generates a Utility Key Event on Open or Generates a Utility Key Event on Open a...

Page 29: ...ional patents may also apply Digiplex is a trademark or registered trademark of Paradox Security Systems Ltd or its affiliates in Canada the United States and or other countries Windows is a registere...

Page 30: ...ay to Friday from 8 00 a m to 8 00 p m EST For technical support outside Canada and the U S call 00 1 450 491 7444 Monday to Friday from 8 00 a m to 8 00 p m EST Please feel free to visit our website...

Reviews: