Rang
e
Status
Explanation
15
Manual Heat Demand
Manual heat demand for central heating is active.
16
Frost Protection
Frost protection mode is active.
19
Reset In Progress
The appliance resets.
21
Halted
The appliance has stopped. It must be reset manually.
23
Factory test
The factory test mode is active.
200
Device Mode
The service tool interface controls the functions of the
appliance.
254
Unknown
The actual state of the appliance is undefined.
Tab.10 AM014 - Sub status
Rang
e
Status
Explanation
0
Standby
The appliance waits for a process or an action.
1
AntiCycling
The appliance waits to restart, because there were too
many consecutive heat demands (anti-short cycle).
4
WaitingForStartCond.
The appliance waits for the temperature to meet the
start conditions.
10
CloseExtGasValve
An external gas valve is opened, when this option is
connected to the appliance. An external option board
must be connected to drive the valve.
12
CloseFlueGasValve
The flue gas valve opens.
13
FanToPrePurge
The fan runs faster to pre-purge.
14
WaitForReleaseSignal
The appliance waits for the release input to close.
15
BurnerOnCommandToSu
A burner start command is sent to the safety core.
17
PreIgnition
Ignition starts before the gas valve opens.
18
Ignition
Ignition is active.
19
FlameCheck
The flame detection is active after the ignition.
20
Interpurge
The fan runs to purge the heat exchanger after a
failed ignition.
30
Normal Int.Setpoint
The appliance operates to reach the desired value.
31
Limited Int.Setpoint
The appliance operates to reach the reduced internal
desired value.
32
NormalPowerControl
The appliance operates on the desired power level.
33
GradLevel1PowerCtrl
The modulation is stopped due to a faster heat ex
changer temperature change than gradient level 1.
34
GradLevel2PowerCtrl
The modulation is set to low load due to a faster heat
exchanger temperature change than gradient level 2.
35
GradLevel3PowerCtrl
The appliance is in blocking mode due to a faster heat
exchanger temperature change than gradient level 1.
36
ProtectFlamePwrCtrl
The burner power is increased due to a low ionisation
signal.
37
StabilizationTime
The appliance is in stabilisation time. Temperatures
should stabilise and temperature protections are
switched off.
38
ColdStart
The appliance runs at start load to prevent cold start
noise.
39
ChResume
The appliance resumes central heating after a domes
tic hot water interruption.
40
SuRemoveBurner
Burner demand is removed from safety core.
41
FanToPostPurge
The fan runs to purge the heat exchanger after the ap
pliance stopped.
44
StopFan
The fan has stopped.
45
LimitedPwrOnTflueGas
The power of the appliance is decreased to lower the
flue gas temperature.
4 Settings