Appendix C: UL 2703 Fire Classification
The system has a Fire Class A rating for low slope roofs with
Type I
modules when the following requirements are met:
•
System is installed over a fire resistant roof covering rated for the application (UL2703, 26.3B)
•
Roof slope is less than 2” per ft
•
Wind Deflector is required on the Northern perimeter of the array.
The system has a Fire Class A rating for low slope roofs with
Type II
modules when the following requirements are met:
•
System is installed over a fire resistant roof covering rated for the application (UL2703, 26.3B)
•
Roof slope is less than 2” per ft
•
Wind Deflector is required on the Northern perimeter of the array.