Remote Logger Unit User Manual
-
16
-
Probe Templates
The format of a template is as follows:
<template> = <id>,<name>,<p0>,<p1>,...,<pn>
To read back the template for a particular probe id use:
env template <id>
To install a new template for a particular probe id use:
env template <template>
To uninstall a template and return to the default use:
env template <id>,0
To read back the names of all active templates use:
env template
Analog Probes
The types of analog sensors are:
l
Temperature
l
Humidity
l
Luminous Intensity
l
Air Pressure
l
Air Velocity
For analog sensors, the template supplies a set of exactly 41 floating-point values (the
mapping), which define the output value over the full range of the sensor input, which
may be 0-5V or 0-10V, depending on probe type.
Digital Probes
The types of digital sensors are:
l
Open/Close Contacts
l
Pulse Count