SMARTZONE UPS USER MANUAL
63
not reflect the date that the battery was last fully charged. The user should change this
date to the UPS install date at completion of installation.
The system is programmed to alert 1095 days (3 years) after the set installed Date. The
user may adjust the replacement notification and alarm by reducing the 1095 days by
the number of days specified in the next two fields.
On the Battery Replacement Notification line, press on the number in front of the Day to
type in the number of days less than 1095 days from the install date when the UPS will
notify the user (via a warning) that the battery cartridges are near end of life. The default
is 372 days. This value has a range from 0 to 730 days. If the default value is not
changed, the warning will alert at 1095 – 372 = 723 days after the installation date. This
warning is intended to allow the user to order replacement battery cartridges and
replace the cartridges before the replacement alarm is triggered. The user should
change this interval based on their company policies for replacing Valve Regulated
Lead-Acid (VLRA) batteries.
On the Battery Replacement Alarm line, press the number in front of the Day to type in
the number of days less than 1095 days from the install date when the UPS will notify
the user (via an alarm) that the battery cartridges should be replaced, the default is 365
days (7 days after the Battery Replacement Notification warning). This value has a
range from 0 to 365 days. If the default value is not changed, the alarm will alert at 1095
– 365 = 730 days (or 2 years) after the installation date. This alarm is intended to notify
the user that the battery cartridges should be replaced now. The user should change
this interval based on their company policies for replacing VLRA batteries.
After making all the necessary changes on each page, press the “Save Config” button
before leaving the individual page to save the changes.
Press the up arrow to go to the previous page. Press the up and over arrow to return to
the Advanced Setting Menu page.
10-20kVA 3-Phase UPS
There are 3 battery setup pages for the 10-20kVA 3-phase UPS units.