PViQ Switched POU
Version 1.0
5
Specifications
Overview
The PViQ switched units have outlet control and circuit monitoring. Web pages, including graphs, are
generated by the unit to monitor power and environmental conditions within the cabinet. No software
other than a web browser is required for operation and several data formats are available. In the PViQ
Switched series, built-in sensors monitor Voltage, Current, instantaneous and cumulative Power, as well
as calculated Power Factor. The PViQ Switched per Outlet series includes all standard PViQ Switched
sensors plus additional current sensors to monitor individual outlet current. Optional external sensors and
network cameras are also available.
Environmental
Temperature
Operating:
10°C (50°F) min
45°C (113°F) max
Storage:
-25°C (-13°F) min
65°C (149°F) max
Humidity
Operating:
5% min 95% max
(non-condensing)
Storage:
5% min 95% max
(non-condensing)
Elevation
Operating:
0 m (0 ft) min
2000 m (6561 ft) max
Storage:
0 m (0 ft) min
15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R
125 Volts, 15 Amp
NEMA 5-20R or L5-20R
125 Volts, 20 Amp
NEMA 6-20R or L6-20R
250 Volts, 20 Amp
IEC-320 C13
125/250 Volt, 15 Amp (North America) or 10 Amp (Global)
1
IEC-320 C19
125/250 Volt, 20 Amp (North America) or 16 Amp (Global)
1
1
Given ratings are per receptacle bank