INSTALLATION INSTRUCTIONS     CM296A

For Technical Support: www.panduit.com/resources/install_maintain.asp

Page 4 of 5

6A

(Previously installed cables removed from view for clarity)

Base

Door

10 AWG
Ground Cable

Incoming
Ground Cable

6.1 Connect the incoming ground cable to the ground stud 

on the base of the enclosure. Use the remaining 
adhesive mounts to manage and secure the hot wire, 
neutral wire and incoming ground cable to the inner 
panel.

6.2 Using one of the supplied 10 AWG Grounding Cables, 

attach one end to the grounding stud on the base, on 
top of the incoming ground, and the other end to the 
grounding stud on the door.

6.3 A second 10 AWG Grounding Cable is to be attached to 

the grounding stud on the base, on top of the other two 
cables, and the other end will be secured to the inner 
panel as shown in Figure 6B.

6.4 Secure the cable ends to the grounding studs on the 

base and the door using the supplied #10 Spring Lock 
Washers and #10-32 Hex Nuts.

6.5 The third 10 AWG Grounding Cable is to be attached to 

the grounding position on the switch and the other end 
will be secured to the inner panel.

6.6 The 12 AWG Grounding Cable is to be attached to the 

power supply and the inner panel. The end without a 
terminal should be attached to the power supply. Refer 
to the power supply instruction sheet for proper wiring 
techniques and safety.

6.7 Secure the three grounding cables (base, switch and 

power supply) to the inner panel using the supplied 
#10-32 x 1/2" Pan Head Screw and #10 Spring Lock 
Washer.

Step 6: Grounding Cable Installation

6B

10 AWG
Ground 
Cable

Inner Panel

12 AWG
Ground 
Cable

10 AWG
Ground 
Cable

Secure
Cables

Here

Summary of Contents for IAEIP66

Page 1: ...2 Conduit Fitting Opening for Industrial Enclosure Gland Plate Inner Panel Important Notice Should Fan Kit P N IAEFK54 be integrated into the enclosure P N IAEIP66 the IP rating of the enclosure shall be reduced to IP54 If the enclosure and any active equipment is located in an environment containing conductive particles that have the potential to cause sparks and shorts or the enclosure is placed...

Page 2: ... the gland plate through the holes on the enclosure 2 2 Verify the gland gasket is flat and positioned evenly between the plate and the enclosure 2 3 Secure the plate to the enclosure using the supplied 10 Flat Washers 10 Split Lock Washers and 10 32 Nuts Torque the nuts to 5 in lbs Step 2 Gland Plate Installation sold separately PANDUIT Part s IAECGP Industrial Automation Enclosure Connector Glan...

Page 3: ... the power supply 4 5 Use the adhesive mounts and PAN TYS to manage the wires and secure them to the inner panel Save a couple adhesive mounts and PAN TYS to manage and secure the incoming power lines to the inner panel Step 4 Wiring Optional Thermostat and Fan 5 1 Refer to the power supply instruction sheet for proper wiring techniques and safety If the power supply is not being connected to the ...

Page 4: ...n top of the other two cables and the other end will be secured to the inner panel as shown in Figure 6B 6 4 Secure the cable ends to the grounding studs on the base and the door using the supplied 10 Spring Lock Washers and 10 32 Hex Nuts 6 5 The third 10 AWG Grounding Cable is to be attached to the grounding position on the switch and the other end will be secured to the inner panel 6 6 The 12 A...

Page 5: ...asp www panduit com Page 5 of 5 7 1 Insert the connector end of the patch cord into an IP67 bulkhead 7 2 Insert the plug end of the patch cord into the corresponding port on the switch 7 3 Insert the provided TAK TYS through the shear forms on the inner panel to manage and secure the patch cords within the enclosure Step 7 Patch Cord Installation 7 Patch Cord TAK TY Switch ...

Reviews: