Basic Rack PDU User Manual
-
9
-
5. Ensure conductors have enough slack (none should be under tension).
6. Feed grommet cap down cord and secure to input gland. Reference the table
below to ensure the grommet cap is torqued correctly.
Gland Size Grommet Cap Torque
M16
1.5 N-m (13 in-lb.)
M20
3.0 N-m (27 in-lb.)
M25
4.0 N-m (35 in-lb.)
M32
M40
15 N-m (132 in-lb.)
M50
20 N-m (177 in-lb.)
M63
30 N-m (266 in-lb.)
7. Re-install removable cover plate with the screws removed in step 1.
8. Connect the other end of the power cord to a suitably rated disconnect device.
9. Switch utility circuit breaker “On”.