12.1.3.
Setting Water Outlet Temperature For Heat Mode
• The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the
internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor
temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water
temperature by control panel setting.
• Outdoor temperature is updated every 30 minutes when operation ON.
12.1.4.
Outdoor Fan Motor Operation
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds
after compressor stops operation.
12.2. Water Pump
12.2.1.
Water Pump Control
1. Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during
this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF
immediately and restart delay after 3 minutes.
2. The system will start checking on the water flow level after operation start for 9 minutes. If water flow level is detected low
continuously for 1 minute, the water pump and compressor will be OFF permanently and OFF/ON control panel LED will blink
(H62 error occurs).
3. The water pump will remain ON when compressor OFF due to thermostat OFF.
Summary of Contents for WHUD30BE51
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 71: ...71 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 72: ...72 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Page 74: ...74 When reinstall the water pipe use grease or water at the joining ...
Page 79: ...79 18 3 Hydraulic Pump Performance ...
Page 82: ...82 19 2 WH UD24BE5 1 WH UD30BE5 1 ...
Page 83: ...83 ...