76
13.6 Indoor Unit Safety
13.6.1 Indoor Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the indoor unit safety control
checking is restarted.
13.7 Auto
Restart
Control
1 When the power supply is cut off during the operation of Air-to-Water Heatpump, the compressor will re-
operate after power supply resumes.
13.8 Indication
Panel
LED Operation
Color Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
If Operation LED is blinking, there is an abnormality operation occurs.
Summary of Contents for (WH-UD12CE5-A-1
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components ...
Page 23: ...23 4 2 Outdoor Unit ...
Page 24: ...24 5 Dimensions 5 1 Indoor Unit ...
Page 25: ...25 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 26: ...26 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 31: ...31 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 35: ...35 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 65: ...65 ...
Page 71: ...71 ...
Page 72: ...72 ...
Page 82: ...82 ...
Page 131: ...131 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 132: ...132 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 149: ...149 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 150: ...150 ...
Page 154: ...154 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 155: ...155 ...