53
12. Installation
Instruction
WH-UD12CE5-A WH-UD14CE5-A WH-UD16CE5-A
(WH-UD12CE5-A-1 WH-UD14CE5-A-1 WH-UD16CE5-A-1)
12.1 Select The Best Location
INDOOR UNIT
There should not be any heat source or steam
near the unit.
A place where air circulation in the room is
good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 800 mm.
Must install on a vertical wall.
When install electrical equipment at wooden
building of metal lath or wire lath, according to
electrical facility technical standard, no electrical
contact between equipment and building is
allowed. Insulator must be installed in between.
Do not install the unit at outdoor. This is designed
for indoor installation only.
When connecting solar pump station cable
between indoor unit and solar pump station, the
distance between both apparatuses shall be 2 ~
8 meters and the length of the said cable must be
shorter than 10 meter.
Failure to do so may lead to abnormal operation
to the system.
OUTDOOR UNIT
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
Avoid installations in areas where the ambient
temperature may drop below -20
°
C.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If outdoor unit installed near sea, region with high
content of sulphur or oily location (e.g. machinery
oil, etc), it lifespan maybe shorten.
When installing the product in a
place where it will be affected by
typhoon or strong wind such as
wind blowing between buildings,
including the rooftop of a building
and a place where there is no
building in surroundings, fix the
product with an overturn prevention
wire, etc. (Overturn prevention
fitting model number: K-KYZP15C)
If piping length is over 30 m, additional refrigerant
should be added as shown in the table.
Piping size
Model
Gas Liquid
Rated
Length
(m)
Max
Eleva-
tion
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Addi-
tional
Refrige-
rant
(g/m)
SDF12C6E5/
UD12CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5 30 3 40 50
SDF14C6E5/
UD14CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5 30 3 40 50
SDF16C6E5/
UD16CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5 30 3 40 50
Example : For SDF12C6E5/UD12CE5**
If piping length is 40m, the quantity of additional
refrigerant should be 500g. [(40-30)m x 50 g/m = 500g]
12.2 Indoor/Outdoor
Unit
Installation Diagram
Summary of Contents for (WH-UD12CE5-A-1
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components ...
Page 23: ...23 4 2 Outdoor Unit ...
Page 24: ...24 5 Dimensions 5 1 Indoor Unit ...
Page 25: ...25 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 26: ...26 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 31: ...31 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 35: ...35 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 65: ...65 ...
Page 71: ...71 ...
Page 72: ...72 ...
Page 82: ...82 ...
Page 131: ...131 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 132: ...132 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 149: ...149 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 150: ...150 ...
Page 154: ...154 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 155: ...155 ...