13.1.6 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 1 minute.
Detection
conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.7 Outside Temperature Current Control
13.1.8 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
a. Trigger heater START condition
o
When the outdoor air temperature is 4°C or below, and discharge temperature is 11.6°C or below.
b. Resetting heater STOP condition
1.
When the outdoor air temperature above 6°C.
2.
When the discharge temperature above 18.9°C.
13.1.9 Low Pressure Protection Control
Purpose:
- To protect the system operation.
- Detection period:
- After compressor on for 5 minutes.
Detection
conditions:
- When detection of Tem above 26°C.
- Calculation of average evaporation temperature (Tem).
- Use outdoor piping temperature sensor.
Tem use the value calculated for discharge temperature setting value.
After
detection:
- Compressor stops restart again after 3 mins.
- When abnormalities continuously generated 60 times within 480 minutes, system stops.
- Protection operation is prohibited.
- Error H42 will be displayed.
Summary of Contents for WH-SXH09D0E8
Page 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 9: ...9 ...
Page 10: ...10 ...
Page 11: ...11 4 1 2 Weekly Timer Setting ...
Page 12: ...12 4 1 3 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Noise Filter Printed Circuit Board ...
Page 77: ...77 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 78: ...78 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 80: ...80 When reinstall the water pipe use grease or water at the joining ...
Page 86: ...86 19 2 Outdoor Unit ...
Page 87: ...87 ...