12. Operation and Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal water setting temperature and water
outlet temperature.
12.1.1 Heating
Operation
12.1.1.1 Thermostat
control
Compressor is OFF when Water Outlet Temperature - Internal Water Setting Temperature > 2°C for continuously
3 minutes.
Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature - Water Inlet Temperature
(temperature at thermostat OFF is triggered) < -3°C.
12.1.2 Setting Water Outlet Temperature for Heat Mode
The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit.
Where by the internal water setting temperature is determined automatically depending on the outdoor
temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the
possibility to shift up or down the target water temperature by control panel setting.
Change in setting water outlet temperature is updated every 30 minutes.
Summary of Contents for WH-SXH09D0E8
Page 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 9: ...9 ...
Page 10: ...10 ...
Page 11: ...11 4 1 2 Weekly Timer Setting ...
Page 12: ...12 4 1 3 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Noise Filter Printed Circuit Board ...
Page 77: ...77 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 78: ...78 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 80: ...80 When reinstall the water pipe use grease or water at the joining ...
Page 86: ...86 19 2 Outdoor Unit ...
Page 87: ...87 ...