3. When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
12.14. Solar operation (Optional)
12.14.1. Solar operation
1. Control according to preset whether Solar Priority is set or not.
2. When tank connection is NOT set at SETTING mode, Solar operation is disabled.
3. When Pump A (from Solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is
requested ON (Refer to figure below).
12.14.2. Solar operation control
When solar priority is SET
1. Operation condition:
a. Solar pump operates if all of the following conditions are fulfilled:-
• Power On. (regardless operation ON or OFF).
• There is operation request from Solar pump station.
• Tank hot water temp is below solar on upper limit temp [EEPROM 1 : 70] C.
2. Stop condition:
a. Solar pump stops operating when:-
• No power supply to unit
OR
• There is
NO
operation request from Solar pump station
OR
• Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77] C.
* heat pump OFF OR operate to room side when solar pump operate during solar priority set.
* booster heater OFF when solar pump operate during solar priority set.
When solar priority is NOT SET
1. Operation condition:
a. Solar pump operates if all of the following conditions are fulfilled:-
• Power On. (regardless operation ON or OFF).
• There is operation request from Solar pump station.
• Tank hot water temp is below solar on upper limit temp [EEPROM 1 : 70] C.
• Heat pump thermo Off in tank mode OR Heat pump operate to room side (During Operation ON and tank mode selected).
2. Stop condition:
a. Solar pump stops operating when:-
• No power supply to unit
OR
• There is
NO
operation request from Solar pump station
OR
• Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77] C.
• Heat pump thermo ON and operate to tank side. (During Operation ON and tank mode selected).
Summary of Contents for WH-SXF12D6E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Page 23: ...23 8 1 2 WH SXF12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Page 26: ...26 9 1 2 WH SXF12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Page 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Page 117: ...117 ...