50
12.1.5. Setting Water Outlet Temperature For Heat Mode
• The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the
internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor
temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water
temperature by control panel setting.
• Change in setting water outlet temperature is updated every 30 minutes.
12.1.5.1. Heating Mode Operation Time Chart
Example
1. 3 ways valve control:
• 3 ways valve switch and fix to heating side
2. Heat pump operate follow normal heating operation.
3. Backup heater operate follow normal operation.
4. Solar 3 way valve operates follow solar operation specification.
12.1.6. Water Temperature Thermo Shift Setting
• Switchs are ignored during “PUMPDW” = ON.
• Switchs are ignored during “STATUS” = ON.
• “ ”, “ ”, “SELECT” switch are ignored if “SETTING” = OFF.
• “CANCEL” switch is ignored if “SETTING” = OFF & “STATUS” = OFF.
• If “SET” Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
• Once enter this setting mode, “SETTING” display is ON.
This setting mode is used to easily shift the target water outlet temperature.
Summary of Contents for WH-SXF12D6E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Page 23: ...23 8 1 2 WH SXF12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Page 26: ...26 9 1 2 WH SXF12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Page 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Page 117: ...117 ...