102
16.5 Self-diagnosis
Method
16.5.1 Connection Capability Rank Abnormality (H12)
Malfunction Decision Conditions:
During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to
determine connection capability rank abnormality.
Malfunction Caused:
1 Wrong model interconnected.
2 Wrong indoor unit or outdoor unit PCB (main) used.
3 Faulty indoor unit or outdoor unit PCB (main).
Abnormality Judgment:
Continue for 90 seconds.
Summary of Contents for WH-SXC09F3E8
Page 37: ...37 10 1 2 Solar Printed Circuit Board Optional ...
Page 55: ...55 57 C 57 C 57 C 57 C ...
Page 56: ...56 ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 57 C 57 C 50 C 50 C ...