Auto Address Setting* from the Remote Controller (CZ-RTC4)
* Auto address setting in Cooling mode cannot be done from the remote controller.
NOTE
●
Selecting each refrigerant system individually for auto address setting
●
Auto address setting for each system: Item code “A1”
1
Press and hold the remote controller timer time
button
and
button simultaneously
for 4 seconds or longer.
2
Next, press either the temperature setting
/
button.
Check that the item code is “A1”.
3
Use either the
button to set the system No. to perform
auto address setting.
4
Then press the
button.
Auto address setting for one refrigerant system begins.
When auto address setting for one system is completed,
the system returns to normal stopped status.
<Approximately 4 – 5 minutes are required.>
During auto address setting, “
” is displayed on
the remote controller. This message disappears when auto
address setting is completed.
5
Repeat the same steps to perform auto address setting for
each successive system.
1
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
2
Press the
or
button to see each me
nu.
If you wish to see the next screen instantly, press the
or
button.
Select “9. Auto address” on the LCD display and
press the
button.
Maintenance func
10. Set elec. consumption
12. Check touch key
Sel.
Page [
] Confirm
20:30 (THU)
11. Set touch key
9. Auto address
3
The “Auto address” screen appears on the LCD
display.
Change the “Code no.” to “A1” by pressing the
or
button.
Auto address
Code no.
O/D unit no.
Sel.
Next
20:30 (THU)
1
A1
4
Select the “O/D unit no.” by pressing the
or
button.
Select one of the “O/D unit no.” for auto address by
pressing the
or
button.
Approximately about 10 minutes are required.
When auto address setting is completed, the units
return to normal stopped status.
START
[
]
20:30 (THU)
CZ-RTC5A
CZ-RTC4
Auto Address Setting from the High-spec Wired Remote Controller (CZ-RTC5A)