11
Table 1-10-2 Necessary Amount of Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
U-72MF1U9
U-72MF1U9E
U-96MF1U9
U-96MF1U9E
42 oz/unit
42 oz/unit
1-9. System Limitations
Table 1-11 System Limitations
Max. No. allowable connected outdoor units
3
Max. capacity allowable connected outdoor units
288,000 BTU/h (24 ton, 84.4 kw)
Max. connectable indoor units
40*¹
Max. allowable indoor/outdoor capacity ratio
50 – 130 %
*1: In the case of 16 ton (type 192,000 BTU/h) or smaller units, the number is limited by the total capacity of the connected indoor
units.
1-10. Installation Standards
Relationship between A/C units and refrigerant tubing
Common solenoid valve kit
●
Multiple indoor units under group control can utilize a solenoid valve kit in common.
●
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kit
Total capacity of indoor units (BTU/h)
160
19.000 < Total capacity < 54.600
56
7.500 < Total capacity < 19.000
●
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.
Outdoor unit
Outdoor unit
Indoor unit
Suction tube
Discharge tube
Liquid tube
Balance tube
Suction tube
Discharge tube
Liquid tube
Gas tube
Liquid tube
4-tube layout
3-tube layout
2-tube layout
Solenoid
valve kit
Indoor unit
Room
Hallway
Indoor unit
Room
Indoor unit
Room
Hallway
Indoor unit
Room
Solenoid
valve kit
Solenoid
valve kit
●
Install the solenoid valve kit 98 ft. or less from the indoor unit.
●
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat noticeable. It
is recommended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.
Desirable
Undesirable
W-3WAY̲ECO-i̲U.indb 11
W-3WAY̲ECO-i̲U.indb 11
2011/11/07 16:29:31
2011/11/07 16:29:31
Summary of Contents for U-72MF1U9
Page 53: ...53 W 3WAY ECO i U indb 53 W 3WAY ECO i U indb 53 2011 11 07 16 29 45 2011 11 07 16 29 45...
Page 54: ...54 W 3WAY ECO i U indb 54 W 3WAY ECO i U indb 54 2011 11 07 16 29 45 2011 11 07 16 29 45...
Page 55: ...55 W 3WAY ECO i U indb 55 W 3WAY ECO i U indb 55 2011 11 07 16 29 45 2011 11 07 16 29 45...