background image

U-5~18MX4XPQ
Urban Multi air conditioner
4PW28163-1

Installation manual

26

4

Set the check operation (without initial refrigerant decision)
following setting mode 2 in the field setting and perform the
check operation. 

The system operates for ±30 minutes and automatically stops
the check operation. 

If no malfunction code is displayed on the remote controller
after the system has stopped, check if the operation is
completed. Normal operation will be possible after 5 minutes.

If a malfunction code is displayed on the remote controller,
correct the malfunction and perform the check operation
again as decribed in "Correcting after abnormal completion
of the test operation" on page 26

In case refrigerant was added without using the leak 
detection function (pre-charging, charging in heating mode)

In the check operation, the following checks and judgement will
be performed:

Check of the stop valve opening

Check for wrong wiring

Check of refrigerant overcharge

Judgement of piping length

It takes ±40 minutes to complete the check operation.

Perform the test operation as decribed in the paragraph "Test
operation procedure" on page 26.

Test operation procedure

1

Close all front panels except the front panel of the electric box.

2

Turn ON the power to all outdoor units and the connected indoor
units.

Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.

3

Make the field setting as described in the paragraph "12.3. Field
setting" on page 23.

4

Press the 

 button once, and set to the SETTING

MODE (H1P led = OFF).

5

Press and hold the 

 button down for 5 seconds or

more. The unit will start the test operation.

The test operation is automatically carried out in cooling
mode, the H2P led will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.

It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.

During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the led display may change, but these are not mal-
functions.

During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the 

 button. The unit will stop after

±30 seconds.

6

Close the front panel in order to let it not be the cause of
misjudgement.

7

Check the test operation results by the led display on the
outdoor unit.

8

When the test operation is fully completed, normal operation will
be possible after 5 minutes. 

Otherwise, refer to "Correcting after abnormal completion of the
test operation" on page 26 to take actions for correcting the
abnormality.

Correcting after abnormal completion of the test operation

The test operation is only completed if there is no malfunction code
displayed on the remote controller. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:

Confirm the malfunction code on the remote controller

After correcting the abnormality, press the 

 button

and reset the malfunction code.

Carry out the test operation again and confirm that the
abnormality is properly corrected.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Normal completion

x

x w x

x

x

x

Abnormal completion

x w w x

x

x

x

BS1  MODE

BS4  TEST

BS3  RETURN

Installation error

Error code

Remedial action

The stop valve of an 
outdoor unit is left 
closed.

E3

E4

F3

UF

Check referring to the table in 
"Additional refrigerant charge" on 
page 17

The phases of the 
power to the outdoor 
units are reversed.

U1

Exchange two of the three phases 
(L1, L2, L3) to make a positive 
phase connection.

No power is supplied 
to an outdoor or 
indoor unit (including 
phase interruption).

U1

U4

Check if the power wiring for the 
outdoor units are connected 
correctly.
(If the power wire is not connected 
to L2 phase, no malfunction display 
will appear and the compressor will 
not work.)

Incorrect 
interconnections 
between units

UF

Check if the refrigerant line piping 
and the unit wiring are consistent 
with each other.

Refrigerant 
overcharge

E3

F6

UF

Recalculate the required amount of 
refrigerant from the piping length 
and correct the refrigerant charge 
level by recovering any excessive 
refrigerant with a refrigerant 
recovery machine.

For the U-5~18MX4, 
the wiring is 
connected to the 
Q1/Q2 (Out Multi)

U7

UF

Remove the wiring from the Q1/Q2
(Out Multi).

Insufficient refrigerant

E4

F3

Check if the additional refrigerant 
charge has been finished correctly.
Recalculate the required amount of 
refrigerant from the piping length 
and add an adequate amount of 
refrigerant.

BS3  RETURN

Summary of Contents for U-5MX4XPQ

Page 1: ...gehandleiding Urban Multi airconditioner Nederlands Manual de instalaci n Acondicionador de aire Urban Multi Espa ol Manuale d installazione Climatizzatore Urban Multi Italiano Urban Multi E Manual de...

Page 2: ...0 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm...

Page 3: ...IT TO OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 1 2 1 2 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 D...

Page 4: ...the installation manual supplied with these units for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R...

Page 5: ...36MX4 U 18MX4 U 18MX4 450 1440 64 U 38MX4 U 18MX4 U 12MX4 U 12MX4 475 1235 61 U 40MX4 U 10MX4 U 12MX4 U 12MX4 500 1300 64 U 42MX4 U 12MX4 U 12MX4 U 12MX4 525 1365 64 U 44MX4 U 8MX4 U 18MX4 U 18MX4 550...

Page 6: ...ak Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions...

Page 7: ...ately bears the weight of the unit NOTE Use filler cloth on the forklift arms to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease Do not use...

Page 8: ...n outdoor and indoor units is 90 m or more the size of the main pipes both gas side and liquid side must be increased Depending on the length of the piping the capacity may drop but even in such a cas...

Page 9: ...e 5 always referring to the installation manual delivered with the kit 4 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upwar...

Page 10: ...of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the m...

Page 11: ...select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For l...

Page 12: ...nd the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The difference between the distance of the outdoor...

Page 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Page 14: ...ting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A4P A8P V1R V2R Power module A3P X1A X4A Co...

Page 15: ...te normally in reversed phase If you connect in reversed phase replace two of the three phases This unit has a reverse phase detection circuit If it is activated only operate the unit after correcting...

Page 16: ...ing sheathed cable 16 V 1 Electric wiring diagram Printed on the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out throug...

Page 17: ...from the indoor units must be connected to the F1 F2 In Out terminals on the PC board in the outdoor unit After installing the interconnecting wires inside the unit wrap them along with the on site re...

Page 18: ...etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is t...

Page 19: ...iring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means...

Page 20: ...nance after installation of the unit BS2 SET BS2 SET BS3 RETURN BS1 MODE When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect...

Page 21: ...ct the cooling mode or heating mode for charging Continue with the automatic charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for chargi...

Page 22: ...e remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediately If it is not as shown above correct the malfunction as ind...

Page 23: ...ly charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the b...

Page 24: ...er malfunction code display on page 21 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode Ready Error...

Page 25: ...ant charging from Start of automatic charging refrigerant as explained page 18 again 11 5 Checks after adding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant...

Page 26: ...arts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished Location of the dip switches leds and buttons Led state Throughout the manual the state of the...

Page 27: ...x Multiple outdoor unit system Master unit a a The state of the H8P multi LED in a multi system shows wich unit is the master unit w slave 1 unit c or slave 2 unit x Only the master unit is connected...

Page 28: ...l refrigerant state Perform the test operation as decribed in the paragraph Test operation procedure on page 26 In case refrigerant was added without using the leak detection function charging in cool...

Page 29: ...he unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the cause of misjudgement 7 Che...

Page 30: ...ystem uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a roo...

Page 31: ...in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment o...

Page 32: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 13 14 3 5 4 2 1 7 8 9 6...

Page 33: ...4PW28163 1...

Reviews: