background image

Installation manual

21

U-5~18MX4XPQ

Urban Multi air conditioner

4PW28163-1

Charging in cooling mode

6.

Start up
Wait while the unit is preparing for charging in cooling mode.

7.

Ready

Press the 

 button once within 5 minutes.

If the 

 button is not pushed within 5 minutes, 

P2

 will be

displayed on the remote controller. Refer to "4 Remote controller
malfunction code display" on page 21.

8.

Operation
When the following led display is shown, open valve A and close
the frontpanel. If the frontpanel is left open, the system can not
operate properly during the refrigerant charging.

*

 = The state of this led is not important.

9.

Complete
If the display on the remote controller shows a flashing

 PE

 code,

charging is almost finished.
When the unit stops operating, close valve A immediately and
check the leds and check if the 

P9

  code is displayed on the

remote controller.

If it is not as shown above, correct the malfunction (as indicated
in the display of the remote controller) and restart the complete
charging procedure. When the charging amount is little, the 

PE

code may not be displayed, but instead the 

P9

  code will be

displayed immediately.

10. Press the 

 button once and the charging is complete.

Record the amount that was added on the additional refrigerant
charge label provided with the unit and attach it on the back side
of the front panel.
Perform the test procedure as described in " In case refrigerant
was added without using the leak detection function (charging in
cooling mode)" on page 25.

3

Normal system display

4

Remote controller malfunction code display

Remote controller heating mode malfunction codes

Remote controller cooling mode malfunction codes

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Pressure control 
(for the first minute)

x c x

x

x

x w

Start up control 
(for the next 2 minutes)

x c x

x

x w x

Waiting for stable 
heating conditions 
(for the next ±15 
minutes (according to 
the system))

x c x

x

x w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c c x w x w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c

*

*

*

*

*

When a malfunction occurs, check the display of the
remote controller and refer to "Remote controller
malfunction code display" on page 21.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c c w w w w

BS4  TEST

BS4  TEST

BS1  MODE

LED 

display

(Default 

status

before 

delivery)

Micro-

computer
operation

monitor

Mode

Ready

/Error

Cooling/Heating 

changeover

Low 

noise

Demand

Multi

Indivi-

dual

Bulk 

(master)

Bulk 

(slave)

HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

Single outdoor 

unit system

c

x

x

w

x

x

x

x

x

Multiple 
outdoor 

unit 

system

Master 

unit

(a)

(a) The state of the H8P (multi) LED in a multi-system shows wich unit is the master 

unit (

w

), slave 1 unit (

c

) or slave 2 unit (

x

). 

Only the master unit is connected to the indoor units with interunit wiring.

c

x

x

w

x

x

x

x

w

Slave 

unit 
1

(a)

c

x

x

x

x

x

x

x

c

Slave 

unit 
2

(a)

c

x

x

x

x

x

x

x

x

Error code 

P8 

recharge 
operation

Close valve A immediately and press the TEST OPERATION 
button once.
The operation will restart from the charging mode judgement 
onwards.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the gas side stop valve is 

opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

Error code 

PA

PH

PC

replace 
cylinder

Close valve A and replace the empty cylinder. When renewed, 
open valve A (the outdoor unit will not stop operating).
The code on the display shows the unit where a cylinder is to be 
renewed:

PA

 = master unit, 

PH

 = slave unit 1, 

PC

 = slave unit 2, flashing 

PA

PH

 and 

PC

 = all units

After recplacing the cylinder, open valve A again and continue the 
work.

P8 

recharge 
operation

Close valve A immediately.
Restart the automatic charging procedure again.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the gas side stop valve is 

opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

- Check if the indoor temperature is not 

lower than 20°C DB

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

*
abnormal 
stop

Close valve A immediately. Confirm the 
malfunction code by the remote controller 
and correct the abnormality by following 
the "Correcting after abnormal completion 
of the test operation" on page 26.

Summary of Contents for U-5MX4XPQ

Page 1: ...gehandleiding Urban Multi airconditioner Nederlands Manual de instalaci n Acondicionador de aire Urban Multi Espa ol Manuale d installazione Climatizzatore Urban Multi Italiano Urban Multi E Manual de...

Page 2: ...0 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm...

Page 3: ...IT TO OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 1 2 1 2 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 D...

Page 4: ...the installation manual supplied with these units for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R...

Page 5: ...36MX4 U 18MX4 U 18MX4 450 1440 64 U 38MX4 U 18MX4 U 12MX4 U 12MX4 475 1235 61 U 40MX4 U 10MX4 U 12MX4 U 12MX4 500 1300 64 U 42MX4 U 12MX4 U 12MX4 U 12MX4 525 1365 64 U 44MX4 U 8MX4 U 18MX4 U 18MX4 550...

Page 6: ...ak Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions...

Page 7: ...ately bears the weight of the unit NOTE Use filler cloth on the forklift arms to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease Do not use...

Page 8: ...n outdoor and indoor units is 90 m or more the size of the main pipes both gas side and liquid side must be increased Depending on the length of the piping the capacity may drop but even in such a cas...

Page 9: ...e 5 always referring to the installation manual delivered with the kit 4 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upwar...

Page 10: ...of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the m...

Page 11: ...select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For l...

Page 12: ...nd the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The difference between the distance of the outdoor...

Page 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Page 14: ...ting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A4P A8P V1R V2R Power module A3P X1A X4A Co...

Page 15: ...te normally in reversed phase If you connect in reversed phase replace two of the three phases This unit has a reverse phase detection circuit If it is activated only operate the unit after correcting...

Page 16: ...ing sheathed cable 16 V 1 Electric wiring diagram Printed on the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out throug...

Page 17: ...from the indoor units must be connected to the F1 F2 In Out terminals on the PC board in the outdoor unit After installing the interconnecting wires inside the unit wrap them along with the on site re...

Page 18: ...etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is t...

Page 19: ...iring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means...

Page 20: ...nance after installation of the unit BS2 SET BS2 SET BS3 RETURN BS1 MODE When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect...

Page 21: ...ct the cooling mode or heating mode for charging Continue with the automatic charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for chargi...

Page 22: ...e remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediately If it is not as shown above correct the malfunction as ind...

Page 23: ...ly charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the b...

Page 24: ...er malfunction code display on page 21 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode Ready Error...

Page 25: ...ant charging from Start of automatic charging refrigerant as explained page 18 again 11 5 Checks after adding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant...

Page 26: ...arts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished Location of the dip switches leds and buttons Led state Throughout the manual the state of the...

Page 27: ...x Multiple outdoor unit system Master unit a a The state of the H8P multi LED in a multi system shows wich unit is the master unit w slave 1 unit c or slave 2 unit x Only the master unit is connected...

Page 28: ...l refrigerant state Perform the test operation as decribed in the paragraph Test operation procedure on page 26 In case refrigerant was added without using the leak detection function charging in cool...

Page 29: ...he unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the cause of misjudgement 7 Che...

Page 30: ...ystem uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a roo...

Page 31: ...in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment o...

Page 32: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 13 14 3 5 4 2 1 7 8 9 6...

Page 33: ...4PW28163 1...

Reviews: