5
- 27
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
F08 Outdoor Air Temperature Sensor (TO
)
Error
Error Detection Method
1.
It is judged an error when open circuit or short circuit.
Error Diagnosis
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor
2-1
Yes
No
SM830195-01̲Mini VRF SYS.indb 27
SM830195-01̲Mini VRF SYS.indb 27
2011/12/20 16:32:39
2011/12/20 16:32:39