
5
- 26
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
F07 Heat Exchanger Inlet Temperature Sensor (C1
)
Error
Error Detection Method
Error Diagnosis
It is judged an error when open circuit or short circuit.
1.
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor
2-1
Yes
No
SM830195-01̲Mini VRF SYS.indb 26
SM830195-01̲Mini VRF SYS.indb 26
2011/12/20 16:32:39
2011/12/20 16:32:39
Summary of Contents for U-4LE1E5
Page 6: ...v ...
Page 28: ...1 22 MEMO ...
Page 46: ...2 18 MEMO ...
Page 60: ...3 14 MEMO ...
Page 133: ...201201 ...