(3) In snowy regions, be sure to install a snow-protection hood and enclosure.
 

Even in regions that do not have heavy snowfall, install a snow-protection roof (such as a snow hood) if the 
unit is installed in a location where snow may build up and fall from the building’s roof or other surface onto 
the unit. (Install the hood so that the coolant supply opening at the top of the unit can be used.)

(4) Take care that operating noise and exhaust do not disturb neighboring buildings or homes.
  In particular, install so that noise-related local environmental standards, if any, are satis

fi

 ed at the border 

with a neighboring dwelling.

(5) Because this gas heat pump A/C may affect other electrical devices with noise, give due consideration when 

installing AC units (both indoors and outdoors) at enough distance (at least 3 m) from the main unit of TVs, 
radios, stereos, intercoms, PCs, word processors, telephones, etc., as well as their antenna cables, signal 
wires, power cords, etc.

(6) Select an installation location so that the length of refrigerant tubing is within the ranges shown in the table 

below.

Warnings (Same for All Models)
*Always use R410A branch tubes (sold separately) when running branching tubes.

1. Warnings about using branch tubes (

) and header tubes sold separately will come packaged with 

the parts sold separately, so be sure to 
refer to those materials.

2. When using a T-tee branch tube 

(provided by installer) (only with L3 at 
2 m or less), the main tubing must be 
either level or vertical. The openings of 
each branch tube must be at a raised 
angle from the ground when the main 
tubing is level. The openings can be set 
at any angle when the main tubing is 
vertical, but be sure to curve a portion 
of the connected tubing upward. Always 
close weld the end point of the T-tee tubing. In addition, pay special attention to the insertion dimensions 
for each connected tube so that refrigerant 

fl

 ow is not blocked at the T-tee branches. Be sure to use only 

standard T-tees.

3. Do not use off the shelf Y-joints (

) for liquid tubes (branch tubes (made on site)).

2-Way Multi Models
Table 1-1 Ranges for Refrigerant Tubing Length and Installation Height Difference

450

560

710

850

450×2 450+560 560×2 450+710 560+710 710×2

Equivalent Horsepower

16

20

25

30

32

36

40

41

45

50

Ratio of capacity for indoor unit to 
outdoor units

50 – 200%

50 – 

170%

Min:  Across the system, a minimum outdoor unit capacity of 50%

Max: Total capacity of 130% with 2 outdoor units

Minimum capacity of indoor units that 
can be connected

Type 22 or greater (equivalent to 0.8 horsepower)

Maximum number of indoor units that 
can be connected (per system)

24

32

48 (A maximum of 24 indoor units can be connected per 
1 outdoor unit)

*  The number of indoor units that can be connected when a W-multi outdoor unit is installed by itself 

is 24 units or fewer.

(Top view)

(Front view)

Required distance from 

fl

 ammable materials

Over 15 cm

Over 60 cm

Over

15 cm

Over

1 cm

Over 1 cm

Fig. 2

Refrigerant tubing side

Over 

5

5 cm

Over 35 cm

Over 

10 cm

Over m

95 cm

Over 95 cm

Over 

2 m

Fig. 1

Over 

10 cm

Over 

10 cm

Maintenance Space

Any angle

Closed weld

Indoor

Outdoor

Indoor

L3<2m

Outdoor

Indoor

Indoor

Indoor

Closed weld

Level line

Raised angle 
(15 to 30 degrees)

Fig. 3 Main tube (horizontal)

Fig. 4 Main tube (vertical)

00-Installation̲All.indb   4

00-Installation̲All.indb   4

2012/09/07   9:32:38

2012/09/07   9:32:38

Summary of Contents for U-16GE2E5

Page 1: ...ECTRICAL SHOCK CAN CAUSE S E V E R E P E R S O N A L I N J U RY OR DEATH ONLY A QUALIFIED EXPERIENCEDELECTRICIANSHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit all wiring and tubing...

Page 2: ...can produce dangerously toxic gas NOTICE The English text is the original instructions Other languages are translation of the original instructions SAFETY PRECAUTIONS Be sure to arrange installation f...

Page 3: ...structure around the outdoor unit If such protections are not installed an injury from falling while working may result Be sure to stand on a stable surface when installing the outdoor unit on an ele...

Page 4: ...the main tubing is level The openings can be set at any angle when the main tubing is vertical but be sure to curve a portion of the connected tubing upward Always close weld the end point of the T te...

Page 5: ...tubing main tubing size 1 2 Outdoor tubing Main tubing Outdoor unit gross capacity kW 45 56 71 85 90 101 112 116 127 142 Gas tube mm 28 58 31 75 31 75 38 1 38 1 Liquid tube mm 12 7 15 88 15 88 19 05 1...

Page 6: ...ndoor units A to B Unit type 22 28 36 45 56 71 80 90 112 140 160 224 280 Tube size Equivalent horsepower 0 8 1 1 3 1 6 2 2 5 3 3 2 4 5 6 8 10 Gas tube mm 12 7 15 88 22 22 25 4 Liquid tube mm 6 35 9 52...

Page 7: ...valve kit purchased separately Externally mounted solenoid valve kit sold separately Branch tube purchased separately Ball valve purchased separately T tee provided by installer Closed pinch weld Fig...

Page 8: ...8 Discharge tube 12 7 Liquid tube 9 52 Table 2 4 Solenoid valve kit indoor unit tubes 2 tube side Indoor unit Unit Type 22 56 kW 71 160 kW Equivalent Horsepower 0 8 2 0 2 5 6 0 Tubing size mm Gas tube...

Page 9: ...els If this condition is not met the system must either be equipped with two of the countermeasures alarm ventilation or safety shut off valve or be redesigned Please note when the system is in the lo...

Page 10: ...eps such as connecting the foundation and the building structure with reinforcing bars in accordance with building utilities earthquake resistant design and construction guidelines Foundation types A...

Page 11: ...pressure or shock to the pipe path In particular take sufficient precautions when installing near roads There is a danger of fire or explosion resulting from fuel gas leakage In regions with heavy sn...

Page 12: ...care that it is not blocked from bending smashing the exhaust drain hose If the exhaust drain hose is blocked it will result in poor engine combustion and may lead to an equipment breakdown Slope the...

Page 13: ...r seamless tubing C1220T Tubing size Choose tubing sizes according to tables 1 2 1 3 1 5 and 2 2 to 2 4 Use tube with thickness as per Table 4 Table 4 Tubing size mm Exterior diameter Wall thickness T...

Page 14: ...it before brazing Cool the tubes with wet cloths or other materials to prevent the value inside the machine from being damaged by the brazing heat Be sure to replace the contents of the tube with nit...

Page 15: ...uffocation and injury to nearby persons Fig 18 Gas tube Liquid tube Pressure gauge Pressure reducing valve Siphon tube Nitrogen When checking for air vacuum tightness do so at all service ports at the...

Page 16: ...ubing G total length in meters of 6 35 mm diameter liquid tubing H Unit additional charge amount Table 7 Be careful to charge accurately according to refrigerant weight Charging procedure Evacuate the...

Page 17: ...tubes that is heat resistant to at least 120 C and at least 80 C for liquid and suction tubes tubes Use separate piping for the power cables and the control cables If the cables are passed through th...

Page 18: ...should the engine need to be replaced Table 8 Engine external dimensions mm Package weight kg Width Depth Height 670 810 640 760 650 700 170 Figures in parentheses are the external dimensions of the w...

Page 19: ...h outdoor unit be sure to install them on the vibration resistant frame Installation on the ground is prohibited When anchoring the refrigerant tubing always anchor the tubing at the main tubing to pr...

Page 20: ...EN 20 NOTE 00 Installation All indb 20 00 Installation All indb 20 2012 09 07 9 32 42 2012 09 07 9 32 42...

Page 21: ...icolo 7 1 delle regolamentazioni 842 EC 2006 NON DISPERDERE R410A NELL ATMOSFERA L R410A UN GAS FLUORATO CAUSA DI EFFETTO SERRA E COPERTO DAL PROTOCOLLO DI KYOTO CON UN POTENZIALE DI RISCALDAMENTO GLO...

Reviews: