13
1-12. Optional Distribution Joint Kits
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 1-12
Model name
Cooling capacity after distribution
Remarks
1. CZ-P680PJ1U
232,000 BTU/h (68.0 kW) or less
For outdoor unit
2. CZ-P1350PJ1U
more than 232,000 BTU/h (68.0 kW)
For outdoor unit
3. CZ-P160BK1U
76,400 BTU/h (22.4 kW) or less*
For indoor unit
4. CZ-P680BK1U
232,000 BTU/h (68.0 kW) or less*
For indoor unit
5. CZ-P1350BK1U
more than 232,000 BTU/h (68.0 kW)*
For indoor unit
n
Tubing size (with thermal insulation)
1. CZ-P680PJ1U
For outdoor unit (Capacity after distribution joint is 232,000 BTU/h (68.0 kW) or less.)
F
E
D
C
HI
H
I
C
C
G
G
G
6-59/64
(175)
5-5/16
(135)
4-21/64
(110)
(97)
3-13/16
4-31/64
(114)
2-53/6
4
(72)
Example:
Gas tubing
Liquid tubing
Distribution
Joint
Distribution
Joint
Reducing
Joints
Reducing
Joints
Unit: in. (mm)
Insulation
Insulation
Table 1-13 Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
Part F
Part G
Part H
Part I
in. (mm)
ø1-3/8"
(ø34.92)
ø1-1/4"
(ø31.75)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
2. CZ-P1350PJ1U
For outdoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW).)
(175)
(135)
(110)
(97)
4-31/64
(114)
2-53/6
4
(72)
B
F
H I
H
I
G
G
G
B
B
A
A
6-57/64
5-5/16
4-21/64
3-13/16
C
C
C
D
D
D
E
F
A
Example:
Gas tubing
Liquid tubing
Distribution
Joint
Distribution
Joint
Insulation
Insulation
: Outside dimension
Reducing
Joints
Reducing
Joints
Unit: in. (mm)
*
With regard to the diameter of the tube without description in Table 1-14, use a reducer (field supply) to adjust the tube diameter.
Table 1-14 Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
Part F
Part G
Part H
Part I
in. (mm)
ø1-3/8"
(ø34.92)
ø1-1/4"
(ø31.75)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
* In case the total capacity of indoor
units connected after distribution
exceeds the total capacity of the
outdoor units, select the distribution
tube size for the total capacity of the
outdoor units.