© Panasonic Industrial Devices SUNX Co., Ltd. 2013 CMJE-SLVVMES2 No.0037-87V
INSTRUCTION MANUAL
Sensor & Wire-saving Link System
S-LINK
VME Bus
S-LINK V
Control Board
SL-VVMES2
Page 1: ... Panasonic Industrial Devices SUNX Co Ltd 2013 CMJE SLVVMES2 No 0037 87V INSTRUCTION MANUAL Sensor Wire saving Link System S LINK VME Bus S LINK V Control Board SL VVMES2 ...
Page 2: ...as short as possible Take care that wrong wiring will damage the product Wiring This product has been developed produced for industrial use only In case noise generating equipment switching regulator inverter motor etc is used in the vicin ity of this product connect the frame ground F G terminal of the equipment to an actual ground This product does not have a dust proof or water proof constructi...
Page 3: ...wo places 2 Push out the knobs to remove SL VVMES2 and pull it out from the VME bus rack 3 If required mount the backplane jumper that corresponds to the slot inside the VME bus rack Notes 1 For details of mounting and removing refer to the instruction manual of VME bus rack 2 When mounting SL VVMES2 be sure to pull out the backplane jumper that corresponds to the slot inside the VME bus rack If t...
Page 4: ...connector for port 2 1 S LINK V terminal block connector for port 1 5 System setting button for port 2 7 BUSY indicator for port 2 Orange 8 Error indicator for port 2 Red 16 5 186 1 169 6 Unit mm 1 S LINK V terminal block connector Connect main line and power supply of S LINK V system Port 1 and port 2 is independent re spectively 7 6 5 4 3 2 1 G D 0 24 0 24 FG IN View from wiring side No Terminal...
Page 5: ...n power is supplied to the computer Changing the mode switch setting during operation is ineffective The setting cannot be changed with the reset command on the S LINK V system side Transmission mode setting switch Transmission mode SW3 1 SW6 1 SW3 2 SW6 2 A mode OFF OFF B mode OFF ON C mode ON OFF A mode ON ON I O control number setting switch I O control number SW3 5 SW6 5 SW3 6 SW6 6 SW3 7 SW6 ...
Page 6: ...Address ON OFF SW2 1 SW5 1 0 to 31 Input Output SW2 2 SW5 2 32 to 63 SW2 3 SW5 3 64 to 95 SW2 4 SW5 4 96 to 127 SW2 5 SW5 5 128 to 159 SW2 6 SW5 6 160 to 191 SW2 7 SW5 7 192 to 223 SW2 8 SW5 8 224 to 255 SW1 1 SW4 1 256 to 287 SW1 2 SW4 2 288 to 319 SW1 3 SW4 3 320 to 351 SW1 4 SW4 4 352 to 383 SW1 5 SW4 5 384 to 415 SW1 6 SW4 6 416 to 447 SW1 7 SW4 7 448 to 479 SW1 8 SW4 8 480 to 511 Note When se...
Page 7: ... main line or the input of the input unit is changed it processes at the interruption level that is set with the interruption level setting switch The above figure indicates the interruption level IRQ1 0 1 SW8 1 2 3 4 5 6 7 8 O N Level 1 2 3 4 5 6 7 8 Unused OFF OFF OFF OFF IRQ1 ON OFF OFF IRQ2 OFF ON OFF IRQ3 ON ON OFF IRQ4 OFF OFF ON IRQ5 ON OFF ON IRQ6 OFF ON ON IRQ7 ON ON ON Note Settings othe...
Page 8: ...gister R 2 bytes 1 word 0152H Bank change over response register R 2 bytes 1 word 0054H Communication stop Reset R W 2 bytes 1 word 0154H Communication stop Reset R W 2 bytes 1 word 0056H Input hold Input change interruption Input change interruption oc currence condition Error interruption R W 2 bytes 1 word 0156H Input hold Input change interruption Input change interruption oc currence conditio...
Page 9: ... 0119 207 206 205 204 203 202 201 200 HL00 001A HL00 011A 215 214 213 212 211 210 209 208 HL00 001B HL00 011B 223 222 221 220 219 218 217 216 HL00 001C HL00 011C 231 230 229 228 227 226 225 224 HL00 001D HL00 011D 239 238 237 236 235 234 233 232 HL00 001E HL00 011E 247 246 245 244 243 242 241 240 HL00 001F HL00 011F 255 254 253 252 251 250 249 248 HL00 0020 HL00 0120 263 262 261 260 259 258 257 25...
Page 10: ...73 472 HL00 003C HL00 013C 487 486 485 484 483 482 481 480 HL00 003D HL00 013D 495 494 493 492 491 490 489 488 HL00 003E HL00 013E 503 502 501 500 499 498 497 496 HL00 003F HL00 013F 511 510 509 508 507 506 505 504 2 HL00 0040 to 1 HL00 0140 to 1 Transmission mode I O control points read out only Transmission mode and I O control points are stored HL00 0040 HL00 0140 bit 7 6 5 4 3 2 1 0 I O contro...
Page 11: ...367 Address 480 to 495 Address 112 to 127 Address 240 to 255 Address 368 to 383 Address 496 to 511 0 Input 1 Output 4 HL00 0046 to 7 HL00 0146 to 7 S LINK V I O unit connected node number read out only It shows the number of nodes to which S LINK V I O units are connected 0 to 256 nodes 5 HL00 004A to B HL00 014A to B Error No Error state read out only bit 0 to 3 Occurred error No is displayed 0H ...
Page 12: ...00 004C or HL00 014C bit 4 to execute and the clearance is completed when HL00 004E or HL00 014E bit 4 turns to 0 In case 0 is written into HL00 004C or HL00 014C bit 4 it is ignored After the clearance in case HL00 004C or HL00 014C bit 4 does not return to 0 it will be cleared soon after the next interruption occurs bit 5 Busy indication When the Busy indicator lights up such as during system se...
Page 13: ...12 HL00 0080 to HL00 00BF HL00 0180 to HL00 01BF Address information bank register until 9 over response register has been changed over 3 Even if write into HL00 0051 HL00 0151 HL00 0053 and HL00 0153 it is ignored 10 HL00 0054 to 5 HL00 0154 to 5 Transmission stop Reset In order to stop the transmission of S LINK V system write 0FH into HL00 0054 or HL00 0154 In order to restart it write in the r...
Page 14: ...d in units of one channel bit 3 Error interruption sets whether an interruption occurs or not when an error occurs When bit 3 is 1 an interruption occurs and when bit 3 is 0 the interruption does not occur In case the error interruption is set to effective the interruption occurs with OR operation applied to all error occurrences For contents of error check by 5 HL00 004A to B HL00 014A to B Error...
Page 15: ...2 HL00 0099 HL00 0199 207 206 205 204 203 202 201 200 HL00 009A HL00 019A 215 214 213 212 211 210 209 208 HL00 009B HL00 019B 223 222 221 220 219 218 217 216 HL00 009C HL00 019C 231 230 229 228 227 226 225 224 HL00 009D HL00 019D 239 238 237 236 235 234 233 232 HL00 009E HL00 019E 247 246 245 244 243 242 241 240 HL00 009F HL00 019F 255 254 253 252 251 250 249 248 HL00 00A0 HL00 01A0 263 262 261 26...
Page 16: ...esponse register 02H Error 3 occurred address S LINK V I O unit is indicated When each bit is 1 the S LINK V I O unit connected to the address is disconnected or in er ror In case Bank change over response register 03H Error 4 occurred address S LINK V I O unit is indicated S LINK V I O unit having the allocated address In case Bank change over response register 04H Error 5 occurred address S LINK...
Page 17: ... SL VVMES2 Internal circuit reads out bank number of the bank change over request register SL VVMES2 Internal circuit switches the data area to the information corresponding to the bank number SL VVMES2 The internal circuit switches to the bank change over response register and then writes in the bank number User s computer It reads out bank number of the bank change over response register User s ...
Page 18: ... 00D9 HL00 01D9 207 206 205 204 203 202 201 200 HL00 00DA HL00 01DA 215 214 213 212 211 210 209 208 HL00 00DB HL00 01DB 223 222 221 220 219 218 217 216 HL00 00DC HL00 01DC 231 230 229 228 227 226 225 224 HL00 00DD HL00 01DD 239 238 237 236 235 234 233 232 HL00 00DE HL00 01DE 247 246 245 244 243 242 241 240 HL00 00DF HL00 01DF 255 254 253 252 251 250 249 248 HL00 00E0 HL00 01E0 263 262 261 260 259 ...
Page 19: ...rates interruption Computer I O address hexadecimal S LINK V address Port 1 Port 2 bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 HL00 00F9 HL00 01F9 463 462 461 460 459 458 457 456 HL00 00FA HL00 01FA 471 470 469 468 467 466 465 464 HL00 00FB HL00 01FB 479 478 477 476 475 474 473 472 HL00 00FC HL00 01FC 487 486 485 484 483 482 481 480 HL00 00FD HL00 01FD 495 494 493 492 491 490 489 488 HL00 00FE...
Page 20: ...ability Note 4 1 000V AC for one min between external terminals and ground Insulation resistance Note 4 Z ZZ Vibration resistance Note 4 10 to 150Hz frequency 0 75mm amplitude or acceleration 5G in X Y and Z directions for two hours each Shock resistance Note 4 98m s2 acceleration approx 10G in X Y and Z directions for three times each Grounding method Bracket Floating S LINK V system side Capacit...
Page 21: ...20 MEMO ...
Page 22: ...DIRECT INCIDENTAL SPECIAL OR CON SEQUENTIAL DAMAGES OF ANY KIND GENERAL TERMS AND CONDITIONS 4 OR ANY DAMAGES RESULTING FROM LOSS OF USE BUSINESS INTERRUPTION LOSS OF INFORMATION LOSS OR INACCURACY OF DATA LOSS OF PROFITS LOSS OF SAVINGS THE COST OF PROCUREMENT OF SUBSTITUTED GOODS SERVICES OR TECHNOLOGIES OR FOR ANY MATTER ARISING OUT OF OR IN CONNECTION WITH THE USE OR INABILITY TO USE THE PRODU...