4.1 Control Outputs (OSSD)
The
SG-P□□-M
standard units of this device generates pulse signals from the control outputs
(OSSD1 and OSSD2) to perform self-diagnosis when the power supply is turned ON and
periodically during operation.
When an error occurs, it enters the lockout state and the control outputs (OSSD1 and OSSD2)
are set to OFF.
■
Timing chart
For PNP output
For NPN output
(Note 1)
Extended up to a maximum of 150 μs when the load is a capacitance load.
● Do not control the machine using only one point of the control outputs (OSSD1 and
OSSD2). When an OSSD malfunction occurs, the machine cannot be stopped, which
may cause death or serious injury.
4.1 Control Outputs (OSSD)
4-2
WUME-SGPUM-2