- 5
2. Detailed Settings Function
5
Air-to-Water Indoor Unit
<Procedure of CZ-RTC5>
CZ-RTC5
1
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “8. Detailed settings” on the LCD display
and press the
button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no.
Code no.
Set data
10
3-1
0001
Sel.
Next
20:30 (THU)
3
Select the “Code no.” by pressing the
or
button.
Change the “Code no.” by pressing the
or
button (or keeping it pressed).
4
Select the “Set data” by pressing the
or
button.
Select one of the “Set data” by pressing the
or
button.
Then press the
button.
5
Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
Detailed settings
Unit no.
Code no.
Set data
3-1
0001
Sel.
Next
20:30 (THU)
10
Detailed settings
Unit no.
Code no.
Set data
3-1
Sel.
20:30 (THU)
10
0001
Detailed settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit detailed settings
and restart?
NO
YES
SM830231-00̲Single̲欧州.indb 6
2014/04/04 13:48:32
START
[ ]
20:30 (THU)
[
] Confirm
2. Detailed Settings Function
List of Detailed Setting Items
Item code
Item
.
o
N
Setting data
Description
Type
Indoor unit capacity
0012
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0030 Unit No. 30
System address
0099 Not set (Setting at shipment)
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0064 Unit No. 64
Indoor unit address
0099 Not set (Setting at shipment)
0000 Individual (1:1 = Indoor unit with no group wiring) (Setting at shipment)
Group control address
14
10
11
12
13
0000 Function disabled
0001 Stops automatically 5 minutes after operation starts.
0002 Stops automatically 10 minutes after operation starts.
0123 Stops automatically 615 minutes after operation starts.
0124 Stops automatically 620 minutes after operation starts.
Automatic stop time after
operation start
0125 Stops automatically 625 minutes after operation starts.
0030
0016 125 (Type 125)
80 (Type 80)
0000
35
0001 Only stop time setting is enabled.
None
2WAY SYSTEM
Remote Controller Functions
Air-to-Water (W1) (Setting at shipment)
18
OFF reminder function
for when weekly timer is
used
*Can be set in 5-minute
units.
SM830243-00_欧州向け Air-to-Water(S-80MW1E5他)SM&TRSM.indb 5
2015/09/16 10:47:55
Summary of Contents for S-80MW1E5
Page 6: ... MEMO v SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 6 2015 09 17 9 44 58 ...
Page 8: ... MEMO 1 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 11 43 08 ...
Page 28: ... MEMO 3 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 13 48 ...
Page 30: ... MEMO 4 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 14 40 ...
Page 44: ... MEMO 6 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 15 37 ...
Page 50: ...201509 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 11 42 32 ...