Air-to-Water Indoor Unit
2
Thermo OFF Conditions = a and b and c
a. Cooling mode
b.
Δ
Tw(Cool)
≤
Thermo OFF margin
c. Not in Force Thermo ON
Set temp
-2
+5
Δ
Tw
ON
OFF
ON
Set temp
-2
+5
Δ
Tw
ON
OFF
ON
Cooling
Hea
ti
ng
Thermostat
Thermostat
4. Tank Mode Operation
ON/OFF timing of Tank mode operation is basically the same as Heating mode.
The maximum Water outlet temperature is 65˚C.
The Heat Pump operates at less than 45˚C of the Water outlet temperature and will stop at 45˚C.
After reaching 45˚C, the internal heater continues operating.
3. Cooling Mode Operation
4. Tank Mode Operation