8. Mixed system composed of the water heat exchanger unit and indoor unit

* If the air conditioning system is a mixed system, the water heat exchanger unit must be connected to the

branch 1 connection on the refrigeration piping. Connect the liquid piping connection that leads to the indoor
unit to the refrigerant liquid piping, that leads to the indoor unit, of the water heat exchanger unit. (Figure 7A)

• Two wrenches must be used to remove the flare nuts from the piping connections, as well as to tighten

the flare nuts onto the ends of the piping.

• Be careful to tighten the flare nuts to the torque as per the table below, as the flares on the flare nuts can

become damaged due to over tightening. If the flares become loose or damaged, the refrigerant gas will
leak, which may cause an oxygen deficiency hazard.

Figure 7A  Mixed system piping for a water heat exchanger unit and indoor unit

Outdoor unit

 Branch 1

Water heat exchanger unit

Branch 2

Indoor unit

Indoor unit

Refrigerant liquid piping leading to the outdoor unit

Refrigerant gas piping

Refrigerant liquid piping leading to the indoor unit
(flare connectors)

Summary of Contents for S-250WX2E5

Page 1: ...sonal injury or product or property damage If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem co...

Page 2: ...cant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leakfree connection x Check carefully for leaks before starting the te...

Page 3: ...accidents x Perform the stipulated installation work with full consideration and preparations for the threat of typhoons and other strong winds earthquakes and other emergency situations Faulty instal...

Page 4: ...mage to household effects and other problems Keep indoor drain pipe sections as short as possible Insulate all indoor drain pipe sections Adopt measures to ensure that drain water causes no problems f...

Page 5: ...nnect the tubes and perform brazing 4 Reattach the gas tube liquid tube fastening rubber as they were originally After cutting tube be sure to remove all burrs and finish tubing ends to the correct su...

Page 6: ...the pressure to the airtightness test pressure 4 15 MPa and confirm that there is no leakage Refrigerant leakage can cause suffocation and injury to nearby persons Manifold gauge Pressure gauge Pressu...

Page 7: ...the piping connections as well as to tighten the flare nuts onto the ends of the piping Be careful to tighten the flare nuts to the torque as per the table below as the flares on the flare nuts can b...

Page 8: ...her equipment Inadequate amounts of storage water can result in frequent unit starting and stopping and become the cause of breakdowns 6 For test operation attach a water temperature gauge and flow ra...

Page 9: ...ater temperature declines most rapidly throughout the entire water pipe system prompting automatic opera tion of the cold hot water circulation pump 12 Attach proper hoisting fixtures to the water pip...

Page 10: ...Printed in Japan DG0312 0 Authorized representative in EU Panasonic Testing Centre Panasonic Marketing Europe GmbH Winsbergring 15 22525 Hamburg Germany...

Reviews: