4-Way Cassette
Use or nonuse of R32
refrigerant leakage
detection sensor
Nonuse
Use
Capacity of indoor unit
22~160
~36
45
56
60
73, 90
106~
Refrigerant charge amount (k
g
)
Floor area of the room (m
2
)
82
11.3
11.3
11.3
11.3
11.7
12.0
15.9 (12.0)
84
11.5
11.5
11.5
11.5
11.7
12.0
15.9 (12.0)
86
11.6
11.6
11.6
11.6
11.7
12.0
15.9 (12.0)
88
11.7
11.7
11.7
11.7
11.7
12.0
15.9 (12.0)
90
11.9
11.9
11.9
11.9
11.9
12.0
15.9 (12.0)
92
12.0
12.0
12.0
12.0
12.0
12.0
15.9 (12.0)
94 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 15.9 (12.0)
96 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 15.9 (12.0)
98 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 15.9 (12.0)
100 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 15.9 (12.0)
( ) : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5, U-4LZ2E8, U-5LZ2E8, U-6LZ2E8