4-295
2WAY SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
9
17. Slim Low Static Ducted Type (M1 Type)
Unit specifi cations (B)
MODEL No.
Indoor Unit
S-22MM1E5
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
2.2
2.5
BTU / h
7,500
8,500
Air circulation (Hi / Me / Lo)
m
3
/ h
480 / 420 / 360
Moisture removal (High)
Liters / h
0.3
–
External static pressure (High)
Pa {mmAq}
10 {1.0}: At shipment 30 {3.1}: Using short circuit connection
ELECTRICAL RATINGS
Voltage rating
V
220
230
240
220
230
240
Available voltage range
V
198 - 264
198 - 264
Running amperes
A
0.26
0.26
0.26
0.23
0.23
0.23
Power input
W
36
36
36
26
26
26
Power factor
%
63
60
58
51
49
47
Max. starting amperes
A
–
–
–
–
–
–
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 h)
Fan speeds
3 and Automatic control
Air fi lter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
28 / 27 / 25
Using short circuit connection (Hi / Me / Lo)
dB-A
30 / 29 / 27
Refrigerant tubing connections
Flare type
Refrigerant tube
diameter
Liquid tube
mm (in.)
6.35 (1 / 4)
Gas tube
mm (in.)
12.7 (1 / 2)
Drain connection
OD26 mm
Drain pump
Max. head 500 mm above drain connection
Remote controller
Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories
–
Color (Approximate value)
–
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm (in.)
200 (7-7 / 8)
220 (8-21 / 32)
Width
mm (in.)
750 (29-17 / 32)
1030 (40-35 / 64)
Depth
mm (in.)
640 (25-13 / 64)
745 (29-21 / 64)
Net weight
k
g
(lbs.)
19 (42)
Shipping weight
k
g
(lbs.)
23 (51)
Shipping volume
m
3
(cu.ft)
0.169 (5.97)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
TD831159-04̲2WAY VRF.indb 295
TD831159-04̲2WAY VRF.indb 295
2014/09/08 12:02:49
2014/09/08 12:02:49