Mini VRF SYSTEM
Control Functions - Outdoor unit
1 - 34
1
11. Detailed Settings in EEPROM of Outdoor
Unit
DN
Item
Setting No.
81
Outdoor unit capacity
(Setting when the data is not stored in the EEPROM.
Do not change under normal conditions.)
0=Invalid
15=112
17=140
18=160
8F High static pressure setting
0=Invalid (P)
1=High static pressure mode 1
(For details, see "4. Outdoor Fan Control (7)")
A3 The minimum operating time 1 until defrosting
20=20 minutes
21=21 minutes ,,,,,
40=40 minutes (P)
41 - 90=Never use
(For details, see "8. Defrost Control (2)")
A6 Defrost fan speed select
0=Invalid (P) , 1=LL fan speed
A7 The minimum operating time 3 until defrosting
0=0 minute ,
10=10 minutes ,,,,,
90=90 minutes (P) ,,,,,
120=120 minutes
-1=Invalid
C1 O
2
output change
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
3=Pumpdown control
(For details, see "3. Special Control (3)")
CA The defrost detection temperture setting
-3=-3°C (P) , -6=-6°C , -9=-9°C ,,,,, -30=-30°C
E1 Discharge air temperature control with thermostat OFF
additional time
-20=-20 minutes
-19=-19 minutes ,,,,,
0=0 minute (P) ,,,,,
10=10 minutes
(For details, see "5. Outdoor Unit CCU Control (5)")
EF Indoor unit auto restart setting
0=No control
1=capable of auto restart
2=incapable of auto restart
Never use the DN code unlisted in the following table.
(P) : Factory preset mode
U-4LE2E5, U-5LE2E5, U-6LE2E5
LED2
LED1
SW2
SW1
CN-HPS
RUN
TEST
CN-EXG
STOP
CN-TO
CN-SCG
CHK
CN-MOV1
CN-SILENT
CN-ROM
SA1
CN-OC
CN-EMG
CN-RC
CN-MOV4
CN-TERMINAL
CN-LPS
AP
MODE
A.ADD
DEF
SW4
SW3
CN-SCT
CN-EXL
CN-DISCH
JP001
TD831186-00_欧州向け Mini VRF TD.indb 2
16/06/22 8:32:48
NO. of I/U
SM830258-01_欧州向け_1fan_mini_VRF.indb 34
18/03/06 9:09:54
Summary of Contents for S-22ML1E5
Page 54: ... MEMO 1 44 ...
Page 175: ...201803 ...