CAUTION
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (on the outdoor main
control PCB) from all outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3)
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
Fig. 4-3
(3) Do not install the inter-unit control wiring such as star branch wiring. Star branch wiring causes misaddress setting.
(Fig. 4-4)
Fig. 4-4
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
: Branch point
More than 6.6 ft. (2m) required
Fig. 4-5
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
NO
Branch point