background image

27

English

Safety Precautions

f)  Precautions shall be taken to avoid 

excessive vibration or pulsation to 
refrigerating piping.

g) Ensure protection devices, refrigerating 

piping and 

fi

ttings are well protected 

against adverse environmental effects 
(such as the danger of water collecting and 
freezing in relief pipes or the accumulation 
of dirt and debris).

h) Expansion and contraction of long runs 

piping in refrigerating systems shall be 
designed and installed securely (mounted 
and guarded) to minimize the likelihood 
hydraulic shock damaging the system.

i)  Protect the refrigerating system from 

accidental rupture due to moving furniture 
or reconstruction activities.

j)  To ensure no leaking, 

fi

eld-made 

refrigerant joints indoors shall be 
tightness tested. The test method shall 
have a sensitivity of 5 grams per year of 
refrigerant or better under a pressure of at 
least 0.25 times the maximum allowable 
pressure (>1.04 MPa, max 4.15 MPa). No 
leak shall be detected.

1. Installation (Space)

• Product with 

fl

ammable refrigerants, shall 

be installed according to the minimum room 
area, 

A

min

 (m²) mentioned in Installation 

Instructions.

• In case of 

fi

 eld charge, the effect on 

refrigerant charge caused by the different pipe 
length has to be quanti

fi

 ed, measured and 

labelled.

• Must ensure the installation of pipe-work shall 

be kept to a minimum. Avoid use dented pipe 
and do not allow acute bending.

• Must ensure that pipe-work shall be protected 

from physical damage.

• Must comply with national gas regulations, 

state municipal rules and legislation. Notify 
relevant authorities in accordance with all 
applicable regulations.

• Must ensure mechanical connections be 

accessible for maintenance purposes.

• In cases that require mechanical ventilation, 

ventilation openings shall be kept clear of 
obstruction.

• When disposal of the product, do follow to the 

precautions in #12 and comply with national 
regulations.
Always contact to local municipal of

fi

 ces for 

proper handling.

2. Servicing
2-1. Service personnel

• The system is inspected, regularly supervised 

and maintained by a trained and certi

fi

 ed 

service personnel who is employed by the 
person user or party responsible.

• Ensure the actual refrigerant charge is in 

accordance with the room size within which 
the refrigerant containing parts are installed.

• Ensure refrigerant charge not to leak.
• Any quali

fi

 ed person who is involved with 

working on or breaking into a refrigerant 
circuit should hold a current valid certi

fi

 cate 

from an industry-accredited assessment 
authority, which authorizes their competence 
to handle refrigerants safely in accordance 
with an industry recognised assessment 
speci

fi

 cation.

• Servicing shall only be performed 

as recommended by the equipment 
manufacturer. Maintenance and repair 
requiring the assistance of other skilled 
personnel shall be carried out under the 
supervision of the person competent in the 
use of 

fl

 ammable refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

2-2. Work

• Prior to beginning work on systems containing 

fl

 ammable refrigerants, safety checks are 

necessary to ensure that the risk of ignition 
is minimised. For repair to the refrigerating 
system, the precautions in #2-2 to #2-8 must 
be followed before conducting work on the 
system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 

fl

 ammable gas or vapour being present while 

the work is being performed.

• All maintenance staff and others working 

in the local area shall be instructed and 
supervised on the nature of work being 
carried out.

• Avoid working in con

fi

 ned spaces. Always 

ensure away from source, at least 2 meter of 
safety distance, or zoning of free space area 
of at least 2 meter in radius.

• Wear appropriate protective equipment, 

including respiratory protection, as conditions 
warrant.

• Keep all sources of ignition and hot metal 

surfaces away.

ACXF55-32051_SS1021-1.indb   27

ACXF55-32051_SS1021-1.indb   27

13/10/2021   6:32:27 PM

13/10/2021   6:32:27 PM

Summary of Contents for S-1821PT3H-8

Page 1: ...cho nh ng l n sau Tr c khi l p t ng i l p t n n c h ng d n l p t v y u c u kh ch h ng c t gi b n h ng d n tham kh o sau n y Operating Instructions Air Conditioner 22 41 Before operating the unit pleas...

Page 2: ...ho ng 10 gi y hi n th n v nhi t l C ho c F L p pin 1 2 3 1 K o n p y l ng c a i u khi n 2 L p pin AAA ho c R03 3 y n p A i u ch nh ng h 1 Nh n sau nh n c i t th i gian Nh n n t trong kho ng 5 gi y hi...

Page 3: ...h s d ng 12 13 T m hi u th m 14 V sinh m y i u h a 15 16 Nh ng v n th ng g p 17 20 Th ng tin c n l u 21 Ph ki n Bao g m i u khi n t xa Pin AAA ho c 2 pin R03 gi i u khi n 2 c v t c a gi i u khi n S c...

Page 4: ...em ngh ch ch i v i m y Vui l ng li n h v i i l y quy n ho c chuy n gia v sinh c c b ph n b n trong s a ch a l p t th o v l p l i m y L p t v x l kh ng ng c th g y r r ga i n gi t ch y n Vui l ng ki m...

Page 5: ...i n t xa Th o pin kh i i u khi n t xa n u kh ng s d ng trong th i gian d i Pin m i c ng lo i ph i c l p ng c c nh ch d n Ngu n c p i n Kh ng k o d y ngu n ra kh i c m tr nh b gi t i n Ngu n c p i n Kh...

Page 6: ...gi ng nh b o qu n R410A Vi c v n h nh b o d ng s a ch a v n p l i m i ch t l m l nh ph i c ti n h nh b i c c nh n vi n c o t o v ch ng nh n v ph i c gi i thi u t nh s n xu t B t k ng i n o v n h nh b...

Page 7: ...r H th ng c ki m tra th ng xuy n gi m s t v s a ch a b i nh n vi n b o h nh c o t o v ch ng nh n c thu b i ng i s d ng hay m t t ch c c tr ch nhi m C n m b o vi c n p m i ch t l m l nh th c t c th c h...

Page 8: ...a m t c ch an to n v t t h n l n n th i ra ngo i kh ng kh 2 7 Ki m tra thi t b l m l nh Khi ph i thay i c c thi t b i n ph i s d ng c c thi t b m i ph h p v i m c ch v c c y u c u k thu t theo quy nh...

Page 9: ...c ng kh c c a m i tr ng hay kh ng Vi c ki m tra c ng c n t nh n nh h ng c a th i gian s d ng c a thi t b hay s rung li n t c t c c ngu n nh m y n n hay qu t 6 Ph t hi n m i ch t l nh d b t ch y Trong...

Page 10: ...ti p t tr c khi n p m i ch t l m l nh cho h th ng D n nh n l n h th ng khi qu tr nh n p li u ho n t t n u ch a c l m C n ph i h t s c c n tr ng kh ng c n p m i ch t l nh qu quy nh Tr c khi ti n h nh n...

Page 11: ...b nh ch a c s d ng ph i c quy nh r cho c c m i ch t c thu h i v ph i c d n nh n c n th n cho m i ch t c ngh a l c c b nh ch a c bi t thu h i m i ch t B nh ch a ph i c l p t y c c van gi m p v c c van...

Page 12: ...g gi Gi ph ng lu n th ng kh C nh o gi ngang g p l n xu ng t ng Kh ng c i u ch nh c nh o gi ngang b ng tay C 5 t y ch n cho h ng th i gi C th s d ng i u khi n t xa i u ch nh h ng gi th i nh mong mu n C...

Page 13: ...T V d OFF T T l c 22 00 gi 2 Ch n th i gian 3 X c nh n c i t h y c i t gi nh n hay sau nh n Khi ch h n gi b t c thi t l p m y c th kh i ng s m h n so v i gi thi t l p th c t t c nhi t mong mu n ng l...

Page 14: ...n kh ch COOL L M L NH 26 0 C 28 0 C 79 F 82 F i u khi n ch t kh i ng Khi i n c kh i ph c sau khi m t i n c c qu tr nh s t kh i ng l i sau m t kho ng th i gian v i ch ho t ng v h ng lu ng kh ng kh gi n...

Page 15: ...l c kh v o m t tr c m y ng c v i quy tr nh th o ra 2 ng v nh n n t g n ch t m t tr c m y 3 V n ch t c c c v t c hai b n N t Nh n ng 1 Th o r i c c c v t c hai b n 2 Nh n n t m t tr c m y theo h ng ch...

Page 16: ...n h nh c a b i u khi n t xa c d y n b o hi u l i l c kh A n b o hi u l i l c kh n b o hi u l i l c kh B i u khi n t xa c h n gi B i u khi n t xa c d y c p th ng s k thu t cao B i u khi n t xa c d y K...

Page 17: ...y ra t i c c ng ng l nh v n c ng ng t c th ch y t kh i ngo i tr i Ch qu t gi FAN c v n h nh v kh ng kh tr n n m h n Vi c n y x y ra khi nhi t ph ng t t i nhi t thi t l p ch qu t c v n h nh v m s t ng...

Page 18: ...t C1 c a b trao i nhi t ngo i tr i D ng l ng b t th ng F07 C m bi n nhi t C2 c a b trao i nhi t ngo i tr i Trung t m b t th ng F08 C m bi n nhi t kh ng kh ngo i tr i TO b t th ng F12 C m bi n nhi t h...

Page 19: ...2 S c c m bi n nhi t b trao i nhi t trong nh E2 F10 S c c m bi n nhi t kh ng kh trong nh TA F29 Kh i trong nh PCB EEPROM b t th ng L02 Kh i trong nh ngo i tr i kh ng kh p L03 B n sao c i t a ch kh i t...

Page 20: ...y s kh ng c s d ng trong m t th i gian d i K ch ho t ch FAN QU T GI trong 2 3 gi lo i b tri t h i m c n s t l i trong c c b ph n b n trong Vi c n y gi p ng n ch n s ph t tri n c a n m m c T t i n ngu...

Page 21: ...nhau K hi u n y c th d ng k t h p v i m t k hi u h a h c Trong tr ng h p n y n tu n th c c quy nh c li n quan v h a ch t B O NG Bi u t ng n y cho bi t thi t b d ng m i ch t l m l nh c th g y ch y N u...

Page 22: ...temperature as C or F Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press...

Page 23: ...n More 34 Cleaning the Air Conditioner 35 36 Troubleshooting 37 40 Information 41 Accessories Included Remote control AAA or R03 batteries 2 Remote control holder Screws for remote control holder 2 To...

Page 24: ...e appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Improper installation and handling will cause leakage...

Page 25: ...od of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to prevent electric shock Power supply Do not use a...

Page 26: ...imilar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufac...

Page 27: ...ations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service pe...

Page 28: ...erating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines sh...

Page 29: ...hat cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or con...

Page 30: ...Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when ch...

Page 31: ...ylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recover...

Page 32: ...ventilated The horizontal flap swings up and down automatically Do not adjust the horizontal flap by hand There are 5 options for manual airflow direction The airflow direction can be adjusted as desi...

Page 33: ...Example OFF at 22 00 2 Set the time 3 Confirm the setting To cancel the timer press or then press When ON timer is set the unit may start early before the actual set time in order to achieve the desi...

Page 34: ...he unit within the recommended temperature range COOL 26 0 C 28 0 C 79 F 82 F Auto restart control When power is resumed after a power failure the operation will restart automatically with the last op...

Page 35: ...rille by the reverse procedures of removal 2 Close and push the knobs to secure the intake grille 3 Firmly tighten with screws both side Knob Push Close 1 Remove the screws both side 2 Push the knobs...

Page 36: ...e wired remote controller Filter indicator A Filter indicator Filter indicator Timer Remote Controller High spec Wired Remote Controller Wired Remote Controller Do not operate without an air filter Va...

Page 37: ...ndensation occurs on cold pipes and the condensed water may drip from the outdoor unit Unit switch to FAN operation and air become humid This happens when the room temperature reaches the set temperat...

Page 38: ...ure Sensor TD Abnormal F06 Outdoor Heat Exchanger Liquid Temperature Sensor C1 Abnormal F07 Outdoor Heat Exchanger Center Temperature Sensor C2 Abnormal F08 Outdoor Air Temperature Sensor TO Abnormal...

Page 39: ...emp sensor E1 trouble F02 Indoor Heat Exchanger Temp sensor E2 trouble F10 Indoor Air temperature sensor TA trouble F29 Indoor Unit PCB EEPROM Abnormal L02 Indoor Outdoor Unit Type Mismatch L03 Duplic...

Page 40: ...e used for an extended period Activate FAN mode for 2 3 hours to remove any moisture left in the internal parts thoroughly This is to prevent mould growth Turn off the power supply and unplug the unit...

Page 41: ...s case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together...

Page 42: ...Memo ACXF55 32051_SS1021 1 indb 42 ACXF55 32051_SS1021 1 indb 42 13 10 2021 6 32 29 PM 13 10 2021 6 32 29 PM...

Page 43: ...Memo ACXF55 32051_SS1021 1 indb 43 ACXF55 32051_SS1021 1 indb 43 13 10 2021 6 32 29 PM 13 10 2021 6 32 29 PM...

Page 44: ...1 SS1021 1 Printed in China Panasonic Corporation Website http www panasonic com Panasonic Corporation 2021 ACXF55 32051_SS1021 1 indb 44 ACXF55 32051_SS1021 1 indb 44 13 10 2021 6 32 29 PM 13 10 2021...

Reviews: