AHU Kit – Installation Instructions –
11/2021
Product description
3
Technical data and limitations – PACi systems –
R410A
(cont.)
AHU Kit
PAW-280PAH2(L/M) or PAW-280PAH3M(-1)
Outdoor unit – PACi Elite
U-36PE2E5A
U-50PE2E5A
U-60PE2E5A
U-71PE1E5A
U-100PE1E5A U-125PE1E5A U-140PE1E5A
Nominal cooling capacity
kW
3.6
5.0
6.0
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
4.0
5.6
7.0
8.0
11.2
14.0
16.0
Piping connections
Liquid pipe
Inch (mm)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas pipe
Inch (mm)
1/2 (12,7)
1/2 (12,7)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Piping length
Min / Max
m
3 / 40
3 / 40
3 / 40
5 / 50
5 / 50
5 / 50
5 / 50
Precharged length (
R410A
)
Max
m
30
30
30
30
30
30
30
Additional refrigerant charge (
R410A
) due to larger heat
exchanger volume
g/m
20
20
40
50
50
50
50
Ambient temperature
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
Heating (Min / Max) °C WB
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
AHU unit under “standard conditions”
Air volume flow
Cooling (Min / Max) m³/h
480 / 780
480 / 780
540 / 960
720 / 1,500
840 / 1,980
1,140 / 2,100
1,140 / 2,160
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
– / 1.3
– / 1.3
– / 1.4
– / 1.8
1.7 / 2.1
1.7 / 2.1
1.7 / 2.1
Heat exchanger face area
Min / Max
m
2
– / –
– / –
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
AHU unit under “special conditions A
2
”
Air volume flow,
subject to restrictions
2
Cooling (Min / Max) m³/h
480 / 1,080
480 / 1,080
540 / 1,600
720 / 1,800
840 / 2,400
1,140 / 2,600
1,140 / 2,700
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
– / 1,5
– / 1.5
– / 1.8
– / 2.2
1.7 / 3.0
1.7 / 3.0
1.7 / 3.0
Additional refrigerant charge (
R410A
) due to larger heat
exchanger volume
kg/dm
3
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Max. additional refrigerant charge (
R410A
)
kg
0.18
0.18
0.36
0.36
0.81
0.81
0.81
Max. pipe length
m
30
30
40
40
30
30
30
Max. ambient temp. for pump down
°C
n/a
n/a
35
35
25
25
25
AHU Kit
PAW-280PAH2(L/M) or PAW-280PAH3M(-1)
Outdoor unit – PACi Elite
U-71PE1E8A
U-100PE1E8A U-125PE1E8A U-140PE1E8A U-200PE2E8A U-250PE2E8A
Nominal cooling capacity
kW
7.1
10.0
12.5
14.0
19.5
25.0
Nominal heating capacity
kW
8.0
11.2
14.0
16.0
22.4
28.0
Piping connections
Liquid pipe
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
1/2 (12,7)
Gas pipe
Inch (mm)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
1 (25,4)
1 (25,4)
Piping length
Min / Max
m
5 / 50
5 / 50
5 / 50
5 / 50
5 / 70
5 / 70
Precharged length (
R410A
)
Max
m
30
30
30
30
30
30
Additional refrigerant charge (
R410A
) due to extended
piping length
g/m
50
50
50
50
50
80
Ambient temperature
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-15 / 43
-15 / 43
Heating (Min / Max) °C WB
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
AHU unit under “standard conditions”
Air volume flow
Cooling (Min / Max) m³/h
720 / 1,500
840 / 1,980
1,140 / 2,100
1,140 / 2,160
1,680 / 3,960
2,280 / 4,440
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
– / 1.8
1.7 / 2.1
1.7 / 2.1
1.7 / 2.1
2.3 / 4.3
2.7 / 4.3
Heat exchanger face area
Min / Max
m
2
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.54 / 1.0
0.66 / 1.0
AHU unit under “special conditions A
2
”
Air volume flow,
subject to restrictions
2
Cooling (Min / Max) m³/h
720 / 1,800
840 / 2,400
1,140 / 2,600
1,140 / 2,700
1,680 / 4,300
2,280 / 5,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
– / 2.2
1.7 / 3.0
1.7 / 3.0
1.7 / 3.0
2.3 / 5.7
2.7 / 7.1
Additional refrigerant charge (
R410A
) due to larger heat
exchanger volume
kg/dm
3
0.9
0.9
0.9
0.9
0.9
0.9
Max. additional refrigerant charge (
R410A
)
kg
0.36
0.81
0.81
0.81
1.25
2.51
Max. pipe length
m
40
30
30
30
n/a
n/a
Max. ambient temp. for pump down
°C
35
25
25
25
n/a
n/a
Continued on following page. See footnotes overleaf.