15. Troubleshooting 

Guide 

15.1  Self Diagnosis Function 

  The display screen of wireless remote control unit and the self-diagnosis LEDs (green) on the outdoor printed 

circuit board in the outdoor unit can be used to identify the location of the problem. 
Refer to the table below to identify and solve the cause of the problem, and then re-start the air conditioner 
system. 

  If the problem is solved and operation returns to normal. 

LED 1 illuminates and others LED are off. 

 

Diagnosis 

display 

Abnormality 

or 

protection 

control 

LED 6 LED 5 LED 4 LED 3 LED 2 LED 1

Abnormality 

judgement 

Protection 

operation 

Problem Check 

location 

H11 Indoor/outdoor 

abnormal 
communication 

     O 

After 
operation for 
1 minute 

Indoor fan only 
operation can 
start by 
entering into 
force cooling 
operation 

Indoor/outdoor 
communication not 
establish 

 Indoor/outdoor 

wire terminal 

 Indoor/outdoor 

PCB 

 Indoor/outdoor 

connection wire 

H12 Indoor 

unit 

capacity 
unmatched 

    O  

90s 

after 

power supply 

 Total 

indoor 

capability more than 
maximum limit or  
less than minimum 
limit, or number of 
indoor unit less than 
two. 

 Indoor/outdoor 

connection wire 

 Indoor/outdoor 

PCB 

 Specification and 

combination table 
in catalogue 

H15 Compressor 

temperature 
sensor 
abnormality 

    O 

Continuous 
for 5s  

 Compressor 

temperature sensor 
open or short circuit 

 Compressor 

temperature 
sensor lead wire 
and connector 

H16 Outdoor 

 

current 
transformer 
(CT) 
abnormality 

     O  O 

 

 Current 

transformer 

faulty or compressor 
faulty 

 Outdoor PCB 

faulty or 
compressor 
faulty 

H27 Outdoor 

air 

temperature 
sensor 
abnormality 

     O O  

Continuous 
for 5s 

 Outdoor 

air 

temperature sensor 
open or short circuit 

 Outdoor air 

temperature 
sensor lead wire 
and connector 

H28 Outdoor 

heat 

exchanger 
temperature 
sensor 1 
abnormality 

   O 

Continuous 
for 5s 

 Outdoor 

heat 

exchanger 
temperature sensor 1 
open or short circuit 

 Outdoor heat 

exchanger 
temperature 
sensor 1 lead 
wire and 
connector 

H32 Outdoor 

heat 

exchanger 
temperature 
sensor 2 
abnormality 

   O      

Continuous 
for 5s 

 Outdoor 

heat 

exchanger 
temperature sensor 2 
open or short circuit 

 Outdoor heat 

exchanger 
temperature 
sensor 2 lead 
wire and 
connector 

H33 Indoor/ 

outdoor 
misconnection 
abnormality 

   O    O 

 

 

Indoor and outdoor 
rated voltage 
different 

 Indoor and 

outdoor units 
check 

H36 Outdoor 

gas 

pipe 
temperature 
sensor 
abnormality 

   O  O  

Continuous 
for 5s 

Heating 
protection 
operation only 

Outdoor gas pipe 
temperature sensor 
open or short circuit 

  Outdoor gas pipe 

temperature 
sensor lead wire 
and connector 

Summary of Contents for PAPAMY1604017CE

Page 1: ...rienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to ser...

Page 2: ...Dew Prevention Control Cool 24 13 3 Electronic Parts Temperature Rise Protection 1 Cool 24 13 4 Electronic Parts Temperature Rise Protection 2 Cool 24 13 5 Cooling Overload Control Cool 25 13 6 Heatin...

Page 3: ...efrigeration cycle and result in explosion injury etc 8 Do not add or replace refrigerant other than specified type It may cause product damage burst and injury etc 9 For R410A model use piping flare...

Page 4: ...y cause electrical shock in case of equipment breakdown or insulation breakdown CAUTION 1 Do not install the unit at place where leakage of flammable gas may occur In case gas leaks and accumulates at...

Page 5: ...ressure Level dB A 49 Sound Power Level dB 63 Power Factor 99 98 Maximum Current A 13 6 Maximum Input Power W 3 04k Starting Current A 8 5 Minimum Circuit Ampacity A 20 Dimension Height mm inch 795 31...

Page 6: ...4U CS E9SD3UAW 3 2 kW CS E12RKUAW CS E12RB4UW CS E12SD3UAW Capacity range of connectable indoor units From 3 2 kW to 6 4 kW Piping Length 1 room maximum pipe length m ft 25 82 0 Allowable elevation m...

Page 7: ...1330 360 1690 12 55 19 00 6 0 0 6 0 6 Specifications are subject to change without notice for further improvement Indoor unit capacity Total Heating Capacity kW Input Power W COP W W HSPF Current 230...

Page 8: ...View Side View 1 3 32 39 3 38 3 7 8 3 7 8 24 1 8 Anchor Bolt Pitch 14 13 64 x 24 1 8 34 15 32 5 5 32 3 3 4 1 1 2 5 7 32 1 5 8 14 3 6 3 9 32 5 5 32 1 21 32 3 3 8 x 3 10 1 8 8 9 32 6 9 16 63 64 3 3 16 3...

Page 9: ...P SENSOR PIPE TEMP SENSOR HEAT EXCHANGER EVAPORATOR INTAKE TEMP SENSOR PIPE TEMP SENSOR HEAT EXCHANGER EVAPORATOR PIPE TEMP SENSOR PIPE TEMP SENSOR EXPANSION VALVE A STRAINER EXPANSION VALVE B STRAINE...

Page 10: ...10 5 Block Diagram 1 2 3 1 N L POWER SUPPLY TO INDOOR UNIT A TO INDOOR UNIT B 2 3 FUSE NOISE FILTER SC REACTOR L FUSE FM COMP...

Page 11: ...T WHT WHT WHT WHT CN DISP 1 WHITE CN NMODE 1 WHITE CN DISP 1 WHITE CN DISP 2 WHITE CN NMODE YELLOW ELECTRO MAGNETIC COIL 4 WAY VALVE CRANK CASE HEATER ELECTRO MAGNETIC COIL EXPAND VALVE ELECTRO MAGNET...

Page 12: ...HT AC BLK GRY BLK BLK FUSE1 T 3 15A L 250V FUSE2 T 2 5A L 250V RY PWR RY AC PTC1 PTC2 DB2 DB1 L DB3 CT400 RY C T1 L1 I L2 I L2 O L1 O L L L L L L P N U V W CN FM1 WHITE 1 1 1 1 1 4 1 1 1 6 1 1 1 3 3 8...

Page 13: ...13 8 Printed Circuit Board 8 1 Main Printed Circuit Board CN TH1 CN HOT CN DATA CN EV1 CN HT CN EV2 CN DIS CN TH3 CN TH2 CN TH4 CN PSW1 CN FM1...

Page 14: ...14 8 2 Noise Filter Printed Circuit Board CN COM CN DATA CN WHT CN BLK 8 3 Display Printed Circuit Board CN DISP1 CN NMODE1 CN NMODE2 SW1 SW2 SW3 SW4 SW5 LED1 LED2 LED3 LED4 LED5 LED6...

Page 15: ...onal gas Addi tional refri ge rant Power supply Power supply wire size OD ID connection wire size Gas Liquid Outdoor OD CU 2E18SBU Indoor ID 2 UNITS OF CS E9RKUAW 16700 R410A 3 8 9 52mm 1 4 6 35mm 24...

Page 16: ...ent before installing the outdoor unit HEAT PUMP TYPES ONLY Part name Qty Diagram Application Drain elbow 1 For connecting the drain pipe 10 2 Cutting and Flaring the Piping 1 Please cut using pipe cu...

Page 17: ...on parts you should purchase It is advisable to avoid more than 2 blockage directions For better ventilation multiple outdoor installation please consult authorized dealer specialist 3 8 9 52 mm Gas s...

Page 18: ...4 1 8 613 mm 5 5 32 131 mm 5 8 16 mm 14 3 16 360 5 mm 10 5 Connect the Piping Remove the control board cover resin from the outdoor unit by loosening three screws Connecting the Piping to Outdoor Unit...

Page 19: ...ps of gas side 3 way valve at a torque of 13 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to Open using a hexagon...

Page 20: ...208 230V 60Hz min AWG12 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Terminal Indoor Unit B Unit A Unit B Power Supply Cord Indoor...

Page 21: ...Cooling operation is activated with compressor ON o Outdoor ambient temperature is less than 59 F Control contents o When the above conditions are fulfilled based on outdoor pipe temperature the outd...

Page 22: ...and indoor units Operation start condition o Powerful operation ON for targeted indoor unit Operation content o If other indoor units where Powerful operation are OFF achieve setting temperature conti...

Page 23: ...ing was pressed afterward the operation lamp of the indoor unit blinks where the attempt is made to establish the heating operation Its fan is stopped and the air does not discharged o While a heating...

Page 24: ...ions o Outdoor ambient temperature is at protection region as shown in figure below Protection Region Normal Region 89 6 F 86 F OD temp o Outdoor unit total current is above 5 5A Control content o Out...

Page 25: ...q maintain This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation RPM controlled 53 6 F 50 F RPM free OD temp 13 7 Extreme Low Temperature Compre...

Page 26: ...ency will increase However if total outdoor unit running current exceeds Y value compressor will be stopped immediately for 3 minutes Operation Mode CU 2E18SBU X A Y A Cooling Soft Dry A 12 2 17 5 Coo...

Page 27: ...all indoor units 13 15 Valve Close Detection Control This control detects 3 way valve close condition to prevent damage to refrigerant cycle Start conditions o For all connected indoor units if Indoor...

Page 28: ...ion will stop automatically after 15 minutes if PUMP DOWN switch SW1 is not pressed again Pump down operation is not started within 3 minutes after compressor is stopped LED 2 3 4 5 Message Status Pum...

Page 29: ...ng automatic correct example Terminal block From Room B to the living room From Room A to the bedroom NOTE 1 For two rooms connection LED 4 and 5 are not illuminated after wiring operation complete 2...

Page 30: ...ecification and combination table in catalogue H15 Compressor temperature sensor abnormality O O Continuous for 5s Compressor temperature sensor open or short circuit Compressor temperature sensor lea...

Page 31: ...tion short circuit F11 4 way valve switching abnormality O O O O 4 times happen within 30 minutes 4 way valve switching abnormal 4 way valve Lead wire and connector F17 Indoor standby units freezing a...

Page 32: ...in 30 minutes Compressor overheat Insufficient refrigerant F98 Total running current protection O O 3 times happen within 20 minutes Total current protection Check refrigeration system Power source or...

Page 33: ...ful of electrostatic discharge 16 1 1 Removing the Cabinet Top Plate and Cabinet Front Plate 1 Remove the cabinet top plate remove the 8 screws 2 Remove the 8 screws 1 on the center 3 at the top and 4...

Page 34: ...w at the right side of the control box and pull out the entire control box 9 Release the control P C Board tab to remove the control P C Board 6 9 8 7 16 1 4 Removing the Propeller Fan and Fan Motor 1...

Page 35: ...35 3 Disconnect the fan motor connector from the control P C Board 4 Loosen the 4 fan motor mounting screws then remove the fan motor 4...

Page 36: ...17 3 89 1 13 1 6 2 5 22 71 6 5 07 0 89 5 23 0 87 5 28 0 87 5 38 0 86 5 92 0 85 6 28 0 84 25 77 5 02 1 01 5 19 1 01 5 25 1 01 5 37 1 01 5 92 1 02 6 28 1 02 29 84 2 4 90 1 16 5 08 1 17 5 15 1 17 5 27 1...

Page 37: ...1 26 29 84 2 5 77 1 43 5 99 1 44 6 07 1 44 6 22 1 45 6 86 1 48 7 29 1 49 32 89 6 5 62 1 55 5 84 1 56 5 92 1 57 6 07 1 58 6 69 1 61 7 10 1 62 35 95 5 42 1 65 5 64 1 67 5 71 1 68 5 86 1 69 6 45 1 70 6...

Page 38: ...16 60 8 14 04 1 69 9 83 2 07 7 80 2 30 6 47 2 51 5 94 2 62 5 73 2 60 5 16 2 48 18 64 4 13 94 1 75 9 59 2 10 7 46 2 32 6 06 2 52 5 53 2 65 5 42 2 66 5 06 2 58 20 68 13 83 1 82 9 35 2 13 7 13 2 34 5 65...

Page 39: ...1 18 64 4 14 07 1 63 9 68 1 96 7 54 2 16 6 12 2 35 5 58 2 47 5 47 2 48 5 11 2 41 20 68 13 97 1 69 9 44 1 99 7 20 2 18 5 71 2 36 5 16 2 49 5 15 2 53 5 01 2 51 21 69 8 13 81 1 73 9 23 2 01 7 06 2 20 5 7...

Page 40: ...0 62 000 64 000 10 20 30 40 50 60 70 80 90 100 110 120 Outlet Air F Outdoor Air Temperature F CS E12RKUAW CS E9RKUAW 14000 15000 16000 17000 18000 19000 20000 21000 22000 10 20 30 40 50 60 70 80 90 10...

Page 41: ...62 000 62 200 62 400 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Outlet Air F Piping Length ft CS E12RKUAW CS E9RKUAW 15500 16000 16500 17000 17500 18000 10 15 20 25 30 35 40 45 50 55 60 65 70 75...

Page 42: ...50 55 60 65 70 75 Outlet Air F Outdoor Air Temperature F CS E12RKUAW CS E9RKUAW 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 Capacity Btu h O...

Page 43: ...94 200 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Outlet Air F Piping Length ft CS E12RKUAW CS E9RKUAW 19600 19800 20000 20200 20400 20600 20800 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Ca...

Page 44: ...5 38 41 39 81 57 5 16 1 25 24 23 33 28 31 44 29 10 14 47 76 77 13 11 12 54 3 4 8 9 6 45 52 50 55 58 69 60 I I 61 I I 2 43 51 48 49 80 51 78 79 74 Note The above exploded view is for the purpose of par...

Page 45: ...30 27 FLARE NUT 3 8 2 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302246 29 SOUND PROOR MATERIAL 1 CWG302520 30 SOUND PROOR MATERIAL 1 CWG302521 31 SOUND PROOR MATERIAL 1 CWG302522 32 SENSOR COMPLETE CN DI...

Page 46: ...CXF60 02480 74 ACCESSORY CO DRAIN ELBOW 1 CWG87C900 76 NUT TERMINAL COVER 1 CWH7080300J 77 TERMINAL COVER 1 CWH171035 78 TUBE ASSY LIQUID 1 1 CWT026284 79 TUBE ASSY LIQUID 2 1 CWT026285 80 MANIFOLD TU...

Reviews: