26
8 Test Mode
8.1.
Compulsion Defrost
Defrost start forcibly, to make TEST TERMINAL 1 and 2 touch for an instant. (See the following picture of PCB (CONTROL))
After Defrost starting, it is operated normally of Defrost Control.
8.2.
Compulsion FC Fan start
Compulsion FC Fan drive high speed, to be making short-circuit* of TEST TERMINAL 1 and 3. (See the following picture of
PCB (CONTROL))
Compulsion FC Fan drive is ended when the short-circuit is released.
8.3.
To change the rotation speed of compressor
Starting: To be making short-circuit of TEST0 POINT and GND on the PCB (CONTROL). (See the following picture of PCB
(CONTROL))
To press 1 time "Super Freeze" : Value of compressor rotation 25 r/s
To press 2 times "Super Freeze" :Value of compressor rotation 39 r/s
To press 3 times "Super Freeze" :Value of compressor rotation 43 r/s
To press 4 times "Super Freeze" :Value of compressor rotation 59 r/s
To press 5 times "Super Freeze" :Value of compressor rotation 71 r/s
Ending: To release short-circuit of TEST0 POINT and GND.
8.4.
Cut of waiting compressor start
Compressor start waiting is not operated, when to be making short-circuit* of TEST2 POINT and GND.
It is ended when the short-circuit is released. (See the following picture of PCB (CONTROL))
*: Use short-circuit tool
Picture of PCB (CONTROL)
Summary of Contents for NR-B30FW1
Page 5: ...5 2 Specifications ...
Page 6: ...6 3 General Introduction 3 1 Flow of Refrigerant ...
Page 7: ...7 4 Features 4 1 Features 4 1 1 Super Energy Saving ...
Page 8: ...8 ...
Page 9: ...9 4 1 2 Super Keep Fresh Vitamin Safe ...
Page 10: ...10 ...
Page 11: ...11 ...
Page 12: ...12 4 1 3 Super Hygienic ...
Page 13: ...13 4 2 Functions 1 2 3 4 ...
Page 14: ...14 5 6 7 8 ...
Page 21: ...21 6 Location of Controls and Components 6 1 Display and Control Panel ...
Page 22: ...22 6 2 Components ...
Page 23: ...23 7 Installation Instructions 7 1 Installation Instructions ...
Page 24: ...24 7 2 Getting started ...
Page 25: ...25 ...
Page 29: ...29 10 Troubleshooting Guide 10 1 FC and PC not cooling at all Compressor does not run ...
Page 30: ...30 10 2 PC is not cooling or poor cooling FC cooling condition is normal ...
Page 31: ...31 10 3 FC is poor cooling Compressor run ...
Page 32: ...32 10 4 VC is poor cooling or excessive cooling ...
Page 50: ...50 12 Maintenance 12 1 Automatic Defrosting 12 2 Removing and attaching shelves ...
Page 51: ...51 12 3 Care and cleaning instructions ...
Page 52: ...52 ...
Page 53: ...53 13 Dimensions 13 1 Outside NR B30FW1 ...
Page 54: ...54 13 2 Inside NR B30FW1 ...
Page 55: ...55 13 3 Inside NR B30FW1 ...
Page 56: ...56 14 Schematic Diagram 14 1 Schematic Diagram NR B30FW1 ...
Page 57: ...57 14 2 Wiring Diagram NR B30FW1 ...
Page 58: ...58 15 Exploded View and Replacement Parts List 15 1 Exploded View 1 NR B30FW1 ...
Page 61: ...61 15 3 Exploded View 2 NR B30FW1 ...
Page 64: ...64 15 5 Exploded View 3 NR B30FW1 Bundled parts The parts for left opening doors ...