background image

9

8

System configuration and wiring

System configuration/ general wiring diagram

Standard wiring diagram

• In Case of 3-Phase 200 V (50 W, 100 W)

Personal computer 

(Customer preparation) 

Personal computer 

(Customer preparation) 

* When you use single phase, 

  connect the main power 

  between L1 and L2 terminals.

02

Connector 

for control 

signals (I/O)

* 1

* 1

External speed setting 

Variable resister 5 kΩ 

B characteristic 1/4 W

Brushless

amplifier

change of

Direction 

Run/Stop

command

10

1

01

5V

FIN

GND

I

3

I

4

I

5

I

2

I

1

Power 

supply

input

L1

L2

L3

1

5

6

10

MCCB

Molded Case

(

Circuit Breaker

)

02

Connector 

for control 

signals (I/O)

External speed setting 

Variable resister 5 kΩ 

B characteristic 1/4 W

Brushless amplifier

change of

Direction 

Run/Stop

command

10

1

01

5V

FIN

GND

I

3

I

4

I

5

I

2

I

1

• In Case of 3-Phase 200 V (200 W, 400 W, 750 W)

Power 

supply

input

L1

L2

L3

MCCB

Molded Case

(

Circuit Breaker

)

Grounding

B1

P

L3

L2

L1

* When you use single phase, 

  connect the main power 

  between L1 and L2 terminals.

Grounding

RS485

Digital key pad

connecting

cable

 (option)

Digital key pad

connecting

cable

 (option)

Connector

for (SER).

It cannot be used simultaneously.

It cannot be used simultaneously.

Digital key pad 

(Option)

 

digital display console.

It enables change of 

parameter.

  refer to the Operating

(

Instructions (Overall). 

)

PC connecting cable

 

(option) 

POWER

It cannot be used 

simultaneously.

Motor extension cable

 

(option)

Select if needed (to 10 m). 

Motor extension cable 

(option)

Select if needed (to 10 m). 

RS485

Digital key pad 

(Option)

 

digital display console.

It enables change of 

parameter.

  refer to the Operating

(

Instructions (Overall). 

)

PC connecting cable

 

(option) 

POWER

It cannot be used 

simultaneously.

Be sure to ground 

the grounding terminal. 

 Be sure to ground 

the grounding terminal. 

External

regenerative

resistor

(option) 

External

regenerative

resistor

(option) 

Noise

filter

Noise

filter

Connector

for (SER).

Wiring

 •  In wiring to power supply (outside of equipment) from MCCB, use an electric wire of 1.6 mm 

diameter (2.0 mm

2

) or more both for main circuit and grounding. 

  Apply grounding class D (100 Ω or below) for grounding. 

  Do not tighten the ground wires together, but connect them individually.

  Fastening torque of earth screws to be 0.49 to 0.98 N·m.

 •  For details of parameters, refer to the Instruction Manual (Overall).

 •  For the wiring of communication connector (SER), see P10.

 •  When a personal computer is connected, please use communicating software   "PANATERM  

for  BL" (it is gratis download from URL). 

  Change of parameter and the monitor of operational status can be performed.

  If your PC does not have RS232 port, use RS232-USB converter.
*1  You can use the Console A(option) and a Console A connecting cable 

(option) for connection with the Connector for control signals (I/O)

LOW

STOP

HIGH

RUN

Console A 

(option) 

Function of terminal

Connector for power supply (POWER)

• 50 W, 100 W

Connector on Amplifier Side: Part No. 5569-10A1-210 (Molex Inc.) or equivalent

Terminal 

number 

Terminal 

Symbol

Terminal 

name

Terminal explanation 

3

B

terminal for  

Regenerative 

resistor

Please connect Regenerative resistor of an option  if needed.

Regenerative resistor name:

   100 V type   DV0P2890 (50 Ω)

   200 V type   DV0PM20068 (200 Ω)

5

P

6

L3

Terminal for 

Power supply 

input  

Connect the terminal to commercial power supply conforming to 

voltage specification. When you use single phase, connect the main 

power between L1 and L2 terminals.

8

L2

10

L1

1,2,4,7,9

NC

Do not connect anything to NC.

Terminal for power supply input (POWER)

• 200 W, 400 W, 750 W

Terminal 

number 

Terminal 

Symbol

Terminal 

name

Terminal explanation 

5

B1

terminal for  

Regenerative 

resistor

Please connect Regenerative resistor of an option  if needed.

Regenerative resistor name:

   100 V type   DV0P2890 (50 Ω)

   200 V type   DV0PM20068 (200 Ω)

4

P

3

L3

Terminal for 

Power supply 

input  

Connect the terminal to commercial power supply conforming to 

voltage specification. When you use single phase, connect the main 

power between L1 and L2 terminals.

2

L2

1

L1

Recommended Pin Terminal: NICHIFU TERMINAL Ind. TGN TC-1.25-11T

Summary of Contents for MINAS-BL KV Series

Page 1: ... after reading and read as necessary Be sure to give this Instruction manual to an end user Label of safety precaution is affixed to the product If you are the first user of this product please be sure to read the instruction Manual Overall from our Web Site Web address of Panasonic Corporation http industrial panasonic com ww i_e 25000 motor_fa_e motor_fa_e html This product image is 200 W type o...

Page 2: ...urrent protection earth leakage breaker over temperature protecter and emergency stop device must be installed The failure could result in electric shocks injuries or fire Transportation wiring and checking must be performed with power source turned off and after making sure that there is no risk of electric shock The failure could result in electric shocks or injuries Do not subject the product t...

Page 3: ...ght this product Checking the model of Amplifier and Motor This amplifier is designed for use in combination with a motor to be specified by us Check a name of series rated output voltage specifications you wish to use You must not use any other combinations than those listed below Standard Voltage Out put Amplifier Type Applicable Motor Single phase AC100 to 120 V 50 W MBEK5A1BCV MBMS5AZBL 100 W ...

Page 4: ...otor in corrosive atmosphere such as hydrogen sulfide sulfurous acid chlorine ammonia sulfur gas chloride gas sulfide acid alkali and salt in the atmosphere of combustible gas or in the vicinity of flammables 3 Place not exposed to grinding liquid oil mist iron powder and cutting particle 4 Well ventilated place with little moisture oil or inundation and place far from heat source such as a furnac...

Page 5: ...supply outside of equipment from MCCB use an electric wire of 1 6 mm diameter 2 0 mm2 or more both for main circuit and grounding Apply grounding class D 100 Ω or below for grounding Do not tighten the ground wires together but connect them individually Fastening torque of earth screws to be 0 49 to 0 98 N m For details of parameters refer to the Instruction Manual Overall For the wiring of commun...

Page 6: ...ation Connection of digital key pad of an option is possible digital key pad connecting cable of an option DV0P383 is required The terminal number of a modular jack is the following figure 8 1 Refer to operation manual Overall for the correspondence procedure of RS485 1 Do not connect anything 2 5 V DC5 V power supply for digital key pad 3 SOT Interface for digital key pad or PANATERM for BL 4 SIN...

Page 7: ...fier Conformance to EC directive and UL standard Conformance to EC directive and UL standard Configuration of peripheral equipment Power supply 100 V system Single phase 100 V to 120 V 10 50 60 Hz 200 V system Single phase 3 phase 200 V to 240 V 10 50 60 Hz Use the equipment under the environment of overvoltage category II specified by IEC60664 1 In order to obtain overvoltage category III insert ...

Page 8: ...void inputting a supply voltage which significantly exceeds the rated range to the power supply of this product Failure to heed this caution may result in damage to the internal parts causing smoking and or a fire and other trouble Item Specifications Model name Brushless amplifier MBEK 5A1BCV MBEK 5A5BCV MBEK 011BCV MBEK 015BCV MBEK 021BCV MBEK 025BCV MBEK 045BCV MBEK 083BCV Brushless motor MBMS5...

Page 9: ... can be downloaded from the following web site http industrial panasonic com ww i_e 25000 motor_fa_e motor_fa_e html Pursuant to at the directive 2004 108 EC article 9 2 Panasonic Testing Centre Panasonic Marketing Europe GmbH Winsbergring 15 22525 Hamburg F R Germany 7 1 1 Morofuku Daito Osaka 574 0044 Japan Phone 81 72 871 1212 For your records The model number and serial number of this product ...

Reviews: