12.6.3 Communication command and data item table
Modbus
function code
Data item
Data
03H
0000H
Use in the system
(Never use function code 06H. If
function code 06H is sent to the
KT4H/B, the KT4H/B may not be
operable.)
03H/06H
0001H
SV
Set value, Decimal point ignored
03H/06H
0003H
Auto-tuning/Auto-reset
0000H: Cancel
0001H: Perform
03H/06H
0004H
OUT1 proportional band
Set value, Decimal point ignored
03H/06H
0005H
OUT2 proportional band
Set value, Decimal point ignored
03H/06H
0006H
Integral time
Set value
03H/06H
0007H
Derivative time
Set value
03H/06H
0008H
OUT1 proportional cycle
Set value
03H/06H
0009H
OUT2 proportional cycle
Set value
03H/06H
000BH
Alarm 1 value
Set value, Decimal point ignored
03H/06H
000CH
Alarm 2 value
Set value, Decimal point ignored
03H/06H
000FH
Heater burnout alarm value
Set value, Decimal point ignored
03H/06H
0012H
Set value lock
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
03H/06H
0015H
Sensor correction
Set value, Decimal point ignored
03H/06H
0016H
Overlap band/Dead band
Set value
03H/06H
0018H
Scaling high limit
Set value, Decimal point ignored
03H/06H
0019H
Scaling low limit
Set value, Decimal point ignored
03H/06H
001AH
Decimal point place
0000H: xxxx
0001H: xxx.x
0002H: xx.xx
0003H: x.xxx
03H/06H
001BH
PV filter time constant
Set value, Decimal point ignored
03H/06H
001CH
OUT1 high limit
Set value
03H/06H
001DH
OUT1 low limit
Set value
03H/06H
001EH
OUT1 ON/OFF action hysteresis
Set value, Decimal point ignored
03H/06H
001FH
OUT2 action mode
0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling
03H/06H
0020H
OUT2 high limit
Set value
03H/06H
0021H
OUT2 low limit
Set value
03H/06H
0022H
OUT2 ON/OFF action hysteresis
Set value, Decimal point ignored
03H/06H
0023H
Alarm 1 type
0000H: No alarm action
0001H: High limit alarm
0002H: Low limit alarm
0003H: High/Low limits alarm
0004H: High/Low limit range alarm
0005H: Process high alarm
0006H: Process low alarm
0007H: High limit alarm with standby
0008H: Low limit alarm with standby
0009H: High/Low limits with standby
03H/06H
0024H
Alarm 2 type
The same as the Alarm 1 type
03H/06H
0025H
Alarm 1 hysteresis
Set value, Decimal point ignored
03H/06H
0026H
Alarm 2 hysteresis
Set value, Decimal point ignored
03H/06H
0029H
Alarm 1 action delayed timer
Set value
03H/06H
002AH
Alarm 2 action delayed timer
Set value