2.2 RS-422 Connection 

Wiring between FP7 communication cassette AFP7CCM1 (RS-422/RS-485 1-ch insulated type) 

and GT series (RS-422/RS-485 type) (RS-422 connection) 

  

 

Wiring between FP7 communication cassette AFP7CCM2 (RS-422/RS-485 2-ch insulated type) 

and GT series (RS-422/RS-485 type) (RS-422 connection) 

 

 

 

 

Summary of Contents for GT series

Page 1: ...PROGRAMMABLE DISPLAY GT series FP7 Connection Manual WUME GTCONFP7 02 2013 11 panasonic net id pidsx global ...

Page 2: ......

Page 3: ...ween GT series and FP7 3 2 1 RS232C Connection 3 2 2 RS 422 Connection 5 2 3 RS 485 Connection 7 3 Settings of GT Series GTWIN 10 3 1 Creating New GT Series Screen Data 10 3 2 Communication Parameters of GT Series 11 3 3 Clock Setting 12 4 Settings for FP7 13 5 FP7 Devices 14 6 Device Setting using GTWIN 16 ...

Page 4: ...e of GT series can be upgraded from tool software GTWIN Firmware files can be also downloaded from our web site http industrial panasonic com ac e dl_center software User registration is required Free of charge Applicable versions to FP7 GT model Applicable version to FP7 GT02 Ver 1 50 or later GT02L Ver 1 40 or later GT05 Ver 2 10 or later GT12 Ver 1 80 or later GT32 Ver 2 20 or later GT32 E Ver ...

Page 5: ... 1 RS232C Connection Wiring between FP7 COM0 port and GT series 24V RS232C type Wiring between FP7 COM0 port and GT series 5V RS232C type Wiring between FP7 communication cassette AFP7CCS1 RS232C 1 ch insulated type and GT series RS232C type ...

Page 6: ...4 Wiring between FP7 communication cassette AFP7CCS2 RS232C 2 ch insulated type and GT series RS232C type Set the on board switch of AFP7CCS2 to 3Wire ...

Page 7: ...unication cassette AFP7CCM1 RS 422 RS 485 1 ch insulated type and GT series RS 422 RS 485 type RS 422 connection Wiring between FP7 communication cassette AFP7CCM2 RS 422 RS 485 2 ch insulated type and GT series RS 422 RS 485 type RS 422 connection ...

Page 8: ...6 Settings on FP7 Set the on board switches of each cassette to RS 422 For RS 422 connection set the termination resistance switches of each cassette to ON ...

Page 9: ...S 485 Connection Wiring between FP7 communication cassette AFP7CCM1 RS 422 RS 485 1 ch insulated type and GT series RS 422 RS 485 type RS 422 connection 1 1 connection PLC multiple connection GT link function ...

Page 10: ...n cassette AFP7CCM2 RS 422 RS 485 2 ch insulated type and GT series RS 422 RS 485 type RS 485 connection 1 1 connection Note As for the PLC multiple and GT link function connections refer to the connection diagrams in the previous page ...

Page 11: ...9 Settings on FP7 Set the on board switches of each cassette to RS 485 For RS 485 connection set the termination resistance switches of each cassette to ON ...

Page 12: ... connect with FP7 Panasonic FP7 series should be selected for PLC Model Select Panasonic FP7 series for PLC Model on the GTWIN screen for creating a new file When selecting a GT model that is not supported for FP7 Panasonic FP7 series cannot be selected for PLC Model Use a GT model supported for FP7 ...

Page 13: ...When communication is not achieved it is considered as an error Wait Set the wait time for a response being returned from PLC after the transmission of a command from GT to PLC When no response is received within the specified wait time the process is retried Display error code Select whether error codes are displayed at the top right of the screen or not when errors including a communication erro...

Page 14: ...ce No Data format Binary DT90054 DT9054 Higher Minute H00 H59 Lower Second H00 H59 SD50 Year Last two digits of year U1 U99 DT90055 DT9055 Higher Day H01 H31 Lower Hour H00 H23 SD51 Month U1 U12 DT90056 DT9056 Higher Year H01 H99 Lower Month H01 H12 SD52 Day U1 U31 DT90057 DT9057 Higher None Lower Day of the week H00 H06 SD53 Hour U0 U23 SD54 Minute U0 U59 SD55 Second U0 U59 SD56 Day of the week U...

Page 15: ... desired unit number When using the PLC multiple connection the unit number specified by GTWIN corresponds to this unit number Baud rate Set the same Baud Rate as that specified in GTWIN GT Configuration Communication Parameters Baud Rate Data length Set the same Data Length as that specified in GTWIN GT Configuration Communication Parameters Data Length Parity Set the same Parity as that specifie...

Page 16: ...egister DT 0 0 999423 F Yes Yes No Unit memory UM 0 0 524287 F Yes Yes Yes Word Input memory WX 0 511 Yes Yes No Output memory WY 0 511 Yes Yes No Internal relay WR 0 2047 Yes Yes No Link relay WL 0 1023 Yes Yes No System relay WS 0 149 No No No Link register LD 0 16383 Yes Yes No Data register DT 0 999423 Yes Yes No System data SD 0 119 No No No Direct input WI 0 63 No No Yes Direct output WO 0 6...

Page 17: ...bers can be specified in the range of 1 to 468 and they are expressed as PB _ before symbols Slot specification As for the devices marked as Yes in Slot in the above table the slot numbers should be specified Slot numbers can be specified in the range of 1 to 16 and they are expressed as S before symbols Bit specification of link register data register and unit memory For using a link register dat...

Page 18: ...ction is set in the GT configuration setting Global device Select when specifying a global device Local device Select when specifying a local device Program block No Set the program block number when selecting Local Device This item is available only when selecting Local Device Slot No Specify a slot number This item is available only when the device with slot specification has been selected Devic...

Page 19: ...r specification input Device type symbol Device No Example For input memory 511F X511F For local device input PB Program block No _ Device type symbol Device No Example For program block No 100 and internal relay R200 PB100_R200 For the case with slot number specification S Slot No Device type symbol Device No Example For slot No 15 and unit memory UM100 S15 UM100 ...

Page 20: ...Record of changes Manual No Date Desceiption of changes WUME GTCONFP7 01 WUME GTCONFP7 02 Mar 2013 Nov 2013 First Edition Second Edition ...

Page 21: ......

Page 22: ...yama cho Kasugai shi Aichi 486 0901 Japan Telephone 81 568 33 7861 Facsimile 81 568 33 8591 panasonic net id pidsx global About our sale network please visit our website Panasonic Industrial Devices SUNX Co Ltd 2013 WUME GTCONFP7 02 November 2013 PRINTED IN JAPAN ...