6-3. Table of FP3/FP5 System Registers
6-3. Table of FP3/FP5 System Registers
81
Number
Description
Default value
Settable range
Memory Allocation
0
Sequence program memory size
8
FP3: 2 to 10k words
(See note 1. on the next page)
FP3(16k type)&FP5: 2 to 16 words
1
Machine language program memory size
0
FP3: 0 to 8k words
(See note 1. on the next page)
FP3(16k type)&FP5: 0 to 14k words
2
Comment memory size
3
Use default value “3”.
3
Unused
–
–
4
Unused
–
–
Internal I/O Setting
5
Counter start No. setting(See note 2.)
200
0 to 256
6
Timer/Counter hold area start No. setting
200
0 to 256
(See note 2. on the next page)
7
Internal relay hold area start No. setting
60
0 to 98
(See note 3. on the next page)
8
Data register hold area start NO. setting
0
0 to 2,04
(See note 3. on the next page)
9
File register hold area start No. setting
0
0 to 22,525
(See note 3. on the next page)
10
Link relay hold area setting for Link 0
0
0 to 64
(See note 3. on the next page)
11
Link relay hold area setting for Link 1
64
64 to 128
(See note 3. on the next page)
12
Link register hold area setting for Link 0
0
0 to 128
(See note 3. on the next page)
13
Link register hold area setting for Link 1
128
128 to 256
(See note 3. on the next page)
14
Step ladder hold/non-hold setting
1(Non-hold)
0:Hold, 1:Non-hold
15
Data output hold/non-hold setting
0(Non-hold)
0:Non-hold, 1:Hold
16 to 19
Unused
–
–
RUN Mode During an Error
20
Duplicate output
0(Disabled)
0:Output disable
1:Output enable
21
Output unit fuse blow
0(Stop)
0:Stop
22
Advanced unit error
0(Stop)
1:Continue
23
I/O verification error
0(Stop)
24
Watchdog timer time out
0(Stop)
0:Stop 1:Continue
(This register No. is only used by the FP5)
Refer to system register No.30
25
Unused
26
Operation error
0(Stop)
0:Stop
27
Remote I/O slave link error
0(Stop)
1:Continue
28
I/O error in the Remote I/O slave station
0(Stop)
29
Unused
–
–
Wait Time Setting
30
Watchdog timer’s time out value
120(300 ms)
4 to 256(10ms to 640ms)
(This register no. is only by the used FP5)
31
Time setting for managing multiple frames
2,600(6.5s)
4 to 32,760(10ms to 81.9s)
32
Data transfer’s wait times setting for
800(2.0s)
4 to 32,760(10ms to 81.9s)
F145(SEND), P145(PSEND)/
F146(RECV), P146(PRECV) instructions,
F152(RMRD), P152(PRMRD)/
F153(RMWT), P153(PRMWT) instructions
(See note 4)
33
Assigned time for a program
5,000(10ms)
1,000 to 65,535
block-edition-in-RUN
(2,000 to 131,070
µ
s)