![Panasonic FP2 Series Technical Manual Download Page 44](http://html1.mh-extra.com/html/panasonic/fp2-series/fp2-series_technical-manual_3724702044.webp)
MEWNET - W Mode
FP2 Multi-wire Link Unit
4 - 4
4.2
PC Link
4.2
PC Link
4.2.1
Preparing to Use PC Link
When using PC link in the W mode, link area allocations must be specified.
.
Notes
D
Allocations must be specified for both link relays and link reg-
isters.
D
PC link communication is carried out on a programmable con-
troller which has been booted in the PC link mode.
4.2.2
Link Area Allocations
Link relays and link registers used with the PC link function are allocated to the link area
of CPU. The link area is allocated by specifying the system register for the CPU.
System register
No. Name
Default
value
Setting range
40
Specification of range of link relays used for
communication
0
0 to 63 words
41
Specification of range of link registers used
for communication
0
0 to 127 words
For PC link 0
42
Starting number for link relay transmission
(no. of first word)
0
0 to 63
43
Link relay transmission size
0
0 to 64 words
44
Starting number for link register
transmission (first number)
0
0 to 127
45
Link register transmission size
0
0 to 127 words
50
Specification of range of link relays used for
communication
0
0 to 63 words
51
Specification of range of link registers used
for communication
0
0 to 127 words
For PC link 1
52
Starting number for link relay transmission
(no. of first word)
64
64 to 127
53
Link relay transmission size
0
0 to 64 words
54
Starting number for link register
transmission (first number)
128
128 to 255
55
Link register transmission size
0
0 to 127 words
Summary of Contents for FP2 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP2 Multi wire Link Unit Technical Manual ARCT1F302E 2 2008 11...
Page 3: ......
Page 8: ......
Page 10: ...General Specifications FP2 Multi wire Link Unit 1 2...
Page 26: ...General Specifications FP2 Multi wire Link Unit 1 18 1 4 Confirming the Design Contents...
Page 28: ...Parts and Its Functions FP2 Multi wire Link Unit 2 2...
Page 36: ...Parts and Its Functions FP2 Multi wire Link Unit 2 10 2 2 Switch Settings...
Page 38: ...Wiring FP2 Multi wire Link Unit 3 2...
Page 42: ...MEWNET W Mode FP2 Multi wire Link Unit 4 2...
Page 52: ...MEWNET W Mode FP2 Multi wire Link Unit 4 12 4 2 PC Link...
Page 54: ...What to Check If a Problem Occurs FP2 Multi wire Link Unit A 2...
Page 61: ...Appendix B Dimensions...
Page 62: ...Dimensions FP2 Multi wire Link Unit B 2...
Page 63: ...Dimensions FP2 Multi wire Link Unit B 3 unit mm in 28 1 102 100 3 937 12 6 0 496 93 3 661...
Page 64: ...Dimensions FP2 Multi wire Link Unit B 4...
Page 67: ......