Window comparator mode
● In this mode, the ON / OFF state of the comparative output is controlled with a flow rate in the set range.
OFF
Comparative
output
Comparative
output
<Within setting range ON>
ON
OFF
<Out of setting range ON>
ON
Flow rate
Flow rate
Smaller threshold Larger threshold
Smaller threshold Larger threshold
Note: Hysteresis of the window comparator mode is approx. 1% F.S. (factory setting). The hysteresis can be changed
in the range of approx. 1 to 8% F.S. For details, refer to “
Hysteresis setting
” in “
9
PRO MODE
.”
Hysteresis mode
● The comparative output ON / OFF state can be controlled with randomly set hysteresis in this mode.
OFF
<Threshold value small side ON>
ON
OFF
<Threshold value large side ON>
ON
Comparative
output
Comparative
output
Flow rate
Flow rate
Smaller threshold Larger threshold
Smaller threshold Larger threshold
Integrated output mode
● The comparative output ON / OFF state can be controlled with randomly set inte-
grated threshold value in this mode.
OFF
<ON when higher than integrated threshold value>
Integrated threshold value
ON
Integrated flow rate
Integrated flow rate
Integrated threshold value
OFF
<OFF when higher than integrated threshold value>
ON
Comparative
output
Comparative
output
Integrated pulse output mode
● In this mode, pulse can be outputted
with each specified integrated value.
For the specified integrated value, refer
to “
13
SPECIFICATIONS
.”
● Take care that if fluid flows in the direc-
tion opposite to the set flow direction,
the integrated pulse is outputted as well.
OFF
Specified integrated value
Approx. 40ms
(fixed value)
ON
Com-
parative
output
Integrated flow rate
7
RUN MODE
● In this mode, flow rate display mode, confirmation of the set value, peak / bottom
hold function and key lock function are available.
In the flow rate display mode, color of the digital display changes in green or red
in conjunction with the comparative output. The color of the main display can be
changed in conjunction with the comparative output 1, while the color of the sub
display can be changed in conjunction with the comparative output 2.
For setting color of the digital display, refer to “
Display color setting
” in “
9
PRO MODE
.”
Flow rate display mode
● Either instantaneous flow rate or integrated flow rate can be indicated on the digital display.
● The integrated value can be reset by key operation or external input while the in-
tegrated flow rate is indicated. (Note 1)
● At the instantaneous flow rate display, 4-digit instantaneous flow rate value is indi-
cated on the main display, while the flow direction is indicated on the sub display.
● When setting flow direction to bi-direction or one-side forward direction, if fluid flows in
the direction opposite to the forward direction display on the main body, the flow rate val-
ue is indicated negatively. In case of one-side reverse direction, if the fluid flows in the
same direction to the forward direction display, the flow rate value is indicated negatively.
● At the integrated flow rate display, 7-digit integrated flow rate value is indicated on
the main display and the sub display.
● When setting flow direction to bi-direction, if fluid flows in the direction to the forward di-
rection display on the main body, the integrated value will be counted up. While if fluid
flows in the opposite direction, the integrated value will be counted down. Further, in case
of one-side forward direction and one-side reverse direction, if fluid flows in the direction
opposite to the set flow direction by mistake, the integrated value will be counted down.
(RUN mode)
(Integrated flow rate display) (Note 2)
Press
(Integrated value reset)
Press
(RUN mode)
Press
/
Hold down for 2 sec.
(Instantaneous flow rate display)
(RUN mode)
Press
Notes: 1) When resetting the integrated value, first set to the integrated value reset input function, then conduct key operation or
input an external signal. For setting the integrated value reset input function, refer to “
CH2 setting
” in “
9
PRO MODE
.”
2) The integrated value will be reset when the power is supplied again at the integrated flow rate display.
Confirmation of the set value
● The threshold value of the comparative output 1 and the output mode can be checked
while holding down UP key when the flow rate is indicated. Meanwhile, the threshold
value of the comparative output 2, the output mode and the integrated value reset input
function can be checked while holding down DOWN key when the flow rate is indicated.
<Display for the set value of comparative output 1>
(RUN mode)
(Threshold value 1)
While holding down
(Threshold value 2)
Blinks alternately
<Display for the set value of comparative output 2>
(RUN mode)
(Threshold value 1)
(Threshold value 2)
While holding down
Blinks alternately
<When CH2 is set to the integrated value reset input function>
(RUN mode)
(Integration reset input function)
While holding down
Notes: 1) When CH2 is set to the teaching function, the set value cannot be checked.
2)
For details of the output mode, refer to “Output mode and threshold value setting mode” in “
8
MENU SETTING MODE
.”
Peak / bottom hold function
● The peak / bottom hold function displays the peak value and bottom value of the
fluctuating flow rate.
(RUN mode)
Peak hold display
Press
Press
Hold down
while pressing
Bottom hold display
Hold down
Key lock function
● The key lock function prevents key operations so that the conditions set in each
setting mode are not inadvertently changed.
● After setting the key lock, “
” will be displayed on the digital display.
<How to set>
(RUN mode)
(RUN mode)
(Key lock set)
Automatic
Hold down for 1 sec.
while pressing
<How to release>
(RUN mode)
(RUN mode)
(Key lock released)
Automatic
Hold down for 3 sec.
while pressing
8
MENU SETTING MODE
● In this mode, the output mode (threshold value setting mode), forcible output func-
tion and zero-point adjustment function can be set.
(RUN mode)
(Output mode)
(Forcible output function)
(Zero-point adjustment function)
Hold down
for 3 sec.
Set content of each item changes by pressing
Press
Press
Press
Output mode and threshold value setting mode
● Output mode and threshold value can be set.
(RUN mode)
(CH1 setting mode) (Note) For the operation of the output mode, refer to the following diagram.
(CH2 setting mode) Conduct same operation with “CH1 setting mode.”
(Threshold value1 setting mode)
Press
Press
Press
Press
Press
/
Threshold value changes by pressing /
Press
/
Press
/
Press
/
Press
/
Press
/
Press
/
Press
/
Press
/
<When output mode is set to the window comparator mode or hysteresis mode>
(Smaller threshold)
<When output mode is set to the integrated output>
(Threshold value 2 setting mode) Conduct same operation with “threshold value 1 setting mode.”
(Output mode)
(Smaller threshold)
(Larger threshold)
Press
Note: If the teaching function is selected at CH2 setting in PRO mode, jumps to the “
Selection of method for loading
input value
” at “
CH2 setting
” under PRO mode.
<Output mode operation>
Sub display
Output mode
Operation
Output OFF mode (Factory setting)
Output OFF
Window comparator mode
Within setting range ON
Out of setting range ON
Hysteresis mode
Smaller threshold value side ON
Larger threshold value side ON
Integrated output mode
ON when higher than integrated threshold value
OFF when higher than integrated threshold value
Integrated pulse output mode
Pulse output
Forcible output function
● The forcible output function is used to turn ON the comparative output forcibly re-
gardless of output mode or threshold value.
● The comparative output turns ON while pressing UP / DOWN key.
(RUN mode)
Forcible output function
(Comparative output 1 ON )
CH1 lights up in red CH2 lights up in red
(Note)
CH1 / 2 light up in red
(Note)
(Comparative output 2 ON )(Comparative output 1 / 2 ON )
Press
Press
Press
Press
/
Press
Note: When CH2 is set to the external input, the comparative output 2 does not operate.
For the setting method of CH2, refer to “
CH2 setting
” in “
9
PRO MODE
.”