60
Operation Manual
FT1020G3 Rev 2.10.4
15.2.1
Entering the Menus during Fire Alarm
By pressing the soft key "Menu" during fire alarm, you will get access to the menu system
(see Access, page 41).
Note:
Access code is required, in this case, a part of the display's alarm window will be
temporarily suppressed to permit the display of the menu system.
The normal alarm window will be automatically displayed again after the escape from the
menu system or 5 minutes after the latest access to the menu system.
The alarm window will also be automatically displayed again if any of the soft keys "Esc
menu" or "ESC" is pressed or push button "SEVERAL ALARMS".
15.2.2
Test Mode Alarm
Regarding Test mode, see chapter "Perform Monthly Test (H1)", page 110 and chapter
"Perform Zone Test (Test mode) (H7)", page 148.
When an alarm point in a zone set in test mode is tested, it is presented in the display as a
fire alarm but with the information "Test mode" added.
No outputs will be activated except the fire door outputs. The test mode alarm will
automatically reset after approx. 10 seconds.
Fire alarm: 002-03
Latest alarm: 003-11
Alarm number 1 (of 1)
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calender and clock
H4 Present system status
H5 Service
H6 FAULT Acknowledge
H7 Perform ZONE TEST
H8 Maintenance
H9 Interlocking outputs and inputs
H10 Change password
Escape
menu
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...