148
Operation Manual
FT1020G3 Rev 2.10.4
28
Perform Zone Test (Test mode) (H7)
Zones can be tested via menu H1, refer to the maintenance standard AS1851 for more
information in regards to the requirements. However, it is also possible to perform a zone
test via menu (H7). Up to 100 zones can be set in test mode.
In test mode, only the alarm points are tested, i.e. no outputs (e.g. OWS or sounders) will
be activated during the test (Alarm devices can be tested via menu H8/S4 and any output
via menu H8/S8 or via EBLWin (when you are logged on).
If a real fire alarm is activated by an alarm point not in test mode, the normal fire alarm
functions will be activated, i.e. fire alarm presentation, outputs (OWS or sounders)
activated, routing equipment (Fire Brigade TX) activated, etc.
See also chapter "Information Area Priority Order", page 22.
One or more zones in test mode are indicated by the LED "Test mode" (L8). The green
polling LED in the 440x detectors will be turned off in test mode.
The zones are set in test mode one a time and the test mode has to be terminated for each
zone one by one.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H7.
H7 Perform ZONE TEST
"
↲
"
Set in test mode
Zone
0
00
Write the zone number
(e.g. 001).
"
↲
"
Set in test mode
Zone
0
01
√
-- End test mode ---------------------------------------------
Zone 001
Press "
↲
" to start the
test mode. Indicated by
"
√
" and a beep. If the
specified zone is not
exist, it will be indicated
with "X" instead of "
√
"
and a beep.
All zones set in test
mode will be shown in
the "End test mode" list.
Use the soft key "
|
" to
toggle between
Set in
test mode
and
End test
mode
list
.
"
|
"
-- Set in test mode --------------------------------------------
Zone _ _ _
√
End test mode
Zone 001
After the testing, select
a zone in the "End test
mode" list and press "
↲
".
The test mode will be
terminated for all zones.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...