Perform Monthly Test (H1)
The FT1020G3 and its associated equipment in a building must be tested on a regular
basis, please refer to the Australian Maintenance standard AS1851 for details regarding
monthly, quarterly and annual test.
In test mode, only the alarm points are tested, i.e. no outputs (no OWS or sounders) will
be activated during the test. (Alarm devices can be tested via menu H8/S4.)
If a real fire alarm is activated by an alarm point not in test mode, the normal fire alarm
functions will be activated, i.e. fire alarm presentation, outputs (sounders or OWS), routing
equipment (Fire Brigade TX) will be activated, etc.
Note
: If FT1020G3 door is left open, the output(s) for external strobe or alarm bell might
be disabled (if set in EBLWin).
See also chapter "The information area priority order", page 22.
See also chapter “Perform ZONE TEST (Test mode) (H7)", page 148
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Menu H1, press "
↵
"
H1 Perform monthly test
"
↵
"
Check that all LEDs light up!
Press
↵
"
↵
"
[ A l l d o t s a r e v i s i b l e ]
The buzzer (in the
C.U.) sounds and all
dots in the display are
shown. All LEDs light
up, including LEDs in
units connected via
I/O Matrix board
4582.
"
↵
"
Zones to be set in test mode:
?
?? ??? ??? ??? Start test:
↵
Up to 4 zones can
be set in test mode
Write zone no, (e.g.
001, 002, 003, 004)
Zones to be set in test
mode 001 002 003 004
Press "
↵
" to start
the test mode.
"
↵
"
Zones in test mode:
001 002 003 004 End test:
↵
LED "Test mode" (L8)
will light up.
Perform the tests.
The zone(s) will
remain in test mode until the test mode is terminated
. The test mode is terminated
in this menu or automatically one hour after the latest alarm test.
You will be automatically logged out 15 minutes after the latest "action" (using any of the keys) but the
zone(s) will
remain in test mode until the test mode is terminated
, see above.
Perform the test as quickly as possible, since the output(s) for routing equipment (Fire Brigade TX) are
disabled (also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be
"disabled" i.e. fire alarm will be detected faster than normal conditions.
In the tested alarm point, the built-in LED will illuminate and the LEDs "Fire" in the FDCIE will illuminate
for approx. 10 seconds, then the alarm point will be automatically reset. There will be a test mode alarm
indication in the FDCIE display.
A detector in test mode can’t generate a fault.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...