121
Operation Manual
FT1020G3 Rev 2.10.4
23.5
Routing Equipment / ASE (H2/B5)
Disabled outputs are listed in menu H4/U1.
Notes
: Outputs for routing equipment (Fire Brigade TX and Fault TX) can be disabled and
re-enabled via this menu however disabling and re-enabling is always carried out via the
ASE itself. Can be useful during an installation and commissioning, when only local alarms
are required.
Disabled output for routing equipment is indicated by LEDs Fault / Disablements "General
disablements" and "Fire Brigade TX".
Disabled output will stay disabled until re-enabled again via this menu.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H2.
H2 Disable or re-enable
"
↲
"
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
Scroll to menu B5.
B5 Routing equipment
Via menu B5 the
standard outputs (fire
and fault) for routing
equipment can be
disabled.
"
↲
"
Disable Routing equipment
Fire
Fault
Use "◄", "►"to toggle
between:
Fire
Fault
Press "
↲
" to disable,
which will be indicated
with "
√
" and a beep.
The "type" will be
automatically shown in
the Re-enable list
"
↲
"
Disable routing equipment
Fire
Fault
√
-- Disabled routing equipment ---------------------------------
Fire alarm routing
Use the soft key "
|
" to
toggle between
Disable
and
Disabled
.
42
Disable routing equipment from the FDCIE is not permitted, it must be disabled from the ASE itself.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...